Siemens Adds a Stainless Steel Intelligent Valve for AI Data Center Cooling

TL;DR: On 11 November 2026 Siemens introduced a stainless steel version of its Intelligent Valve for direct-to-chip rack loop cooling in AI data centers and high-performance computing. Siemens positions it as an alternative to brass that meets stricter wetted-material requirements, and lists integrated flow, temperature and power measurement, rack-level differential pressure control, automatic presetting and open communication interfaces. The release does not claim second-level balancing or chip-level valve mounting, and it publishes no DN range, actuator model or protocol list.
Siemens published the announcement on its global press site under reference HQSIPR202610307483EN, and WebWire carried the same text. The story is narrower than some circulating summaries suggest: this is an existing valve family extended into data center hydronics, not a new valve platform, and several of the performance phrases attached to it in secondary coverage do not appear in Siemens' own wording. This article separates what the release and Siemens product documentation state from what they do not, and explains what the difference means for anyone specifying, operating or stocking these valves.
What did Siemens announce on 11 November 2026?
Siemens announced a stainless steel version of its Intelligent Valve for direct-to-chip rack loop cooling in AI data centers and high-performance computing environments. The valve is positioned as an alternative to brass and other wetted materials, and Siemens says it addresses wetted-material specifications set by leading chip manufacturers and hyperscale data center operators.
The release frames the product as an extension of a liquid cooling portfolio that already spans hydronics, automation, sensing and digital simulation. Nawfal Slimati, EVP Buildings Products at Siemens, is quoted saying that AI is changing data center thermal requirements and that the new valve combines proven hydronic technology with sensing, control and intelligence. Siemens also cites a Mordor Intelligence projection of 22.65% compound annual growth for the global liquid cooling market from 2026 to 2031.
| Item | Detail | Source |
|---|---|---|
| Announcement date | 11 November 2026 | Siemens press release |
| Reference number | HQSIPR202610307483EN | Siemens press release |
| Product | Stainless steel version of the Intelligent Valve | Siemens press release |
| Target application | Direct-to-chip rack loop cooling in AI data centers and HPC | Siemens press release |
| Stated driver | Stricter wetted-material specifications from chip manufacturers and hyperscale operators | Siemens press release |
| Measured variables | Flow, temperature and system performance, measured continuously | Siemens press release |
| Rack-level function | Stable differential pressure, consistent coolant flow, protection against pressure peaks | Siemens press release |
| Control architecture | Local control loops that can run independently of the CDU controller; automatic presetting; open communication interfaces | Siemens press release |
| Media compatibility | Water, water ethylene glycol and water propylene glycol; PG25 named on the product page | Siemens press release and product page |
| Market context | Liquid cooling market CAGR of 22.65% from 2026 to 2031 | Mordor Intelligence, cited by Siemens |
| Not disclosed | DN range, actuator model, protocol list, pressure and temperature ratings, price, availability date | Absent from release and product page |
Is this a new valve or a stainless steel version of an existing one?
It is a stainless steel version of the existing Intelligent Valve, not a new valve platform. The underlying architecture is unchanged: a two-port pressure-independent control valve with integrated flow and temperature measurement, power calculation and a high-resolution actuator, as documented for the ACVATIX EVG and EVF series used in building HVAC.
The distinction matters commercially. A plant already running the ACVATIX family is looking at a material and connection change, not a new control philosophy. The published building-HVAC documentation (datasheet A6V11444716, dated 5 May 2025) describes threaded EVG valves from DN15 to DN50 with nominal flows of 1.5 to 18 m³/h on ISO-228 threads, and flanged EVF valves from DN65 to DN150 with 30 to 170 m³/h on ISO-7005 flanges. Flow measurement is ultrasonic, with stated accuracy of ±2% for water and ±6% for water-ethylene glycol mixtures, and temperature is measured with paired Pt1000 sensors.
Those figures describe the brass building version. Siemens has not published an equivalent table for the stainless steel rack version, so they should not be copied into a data center specification without written confirmation.
How does the valve balance a rack loop?
At rack level the valve holds a stable differential pressure and a consistent coolant flow, and it adapts automatically when servers or complete racks are added, removed or replaced. Local control loops let it keep balancing without waiting for the coolant distribution unit controller, and automatic presetting shortens commissioning.
Two mechanisms are worth separating. The first is pressure control: by holding differential pressure stable at the rack, the valve limits the pressure peaks that Siemens says could cause leakage or damage cold plates during commissioning, operation and maintenance. The second is flow control: the valve measures flow and temperature continuously and adjusts its position, so the heat picked up by the coolant is matched to the load the rack is presenting.
The local control loops are the architecturally interesting part. Because they can operate independently of the CDU controller, a rack can be added or replaced without re-tuning the whole loop from the plant level down. Siemens pairs that with open communication interfaces so the valve can feed the wider automation and monitoring layer rather than staying a standalone device.
What media, connections and compliance does Siemens list?
Siemens lists compatibility with water, water ethylene glycol and water propylene glycol, with PG25 named as an example on the product page. The rack version uses tri-clamp connections that scale from standard to high-flow, is factory-assembled and leak-tested, and is listed as compliant with ASHRAE TC99 and OCP specifications.
- Coolant media. Water, water-ethylene glycol and water-propylene glycol are supported. The building-HVAC datasheet quantifies the measurement penalty for glycol mixtures at ±6% instead of ±2% for water; Siemens has not published an equivalent accuracy figure for the rack version.
- Connections. Tri-clamp fittings, available from standard to high-flow sizes. That is a deliberate departure from the threaded and flanged connections of the HVAC series and matches sanitary-style practice in rack manifolds.
- Build and testing. Each valve is factory-assembled and leak-tested before shipment, which Siemens says reduces on-site work and downtime.
- Compliance claims. The product page cites ASHRAE TC99 and Open Compute Project specifications, plus corrosion resistance and coolant purity as the reasons for the stainless wetted path.
Brass versus stainless steel: what actually changes?
The change is in the wetted path, not the control concept. Stainless steel addresses coolant purity and corrosion requirements that brass can struggle to meet in direct-to-chip loops, while the measured variables, pressure-independent behaviour and local balancing logic stay within the same product family. Siemens has not published a side-by-side material or pressure-rating table.
| Attribute | ACVATIX Intelligent Valve (building HVAC documentation) | New stainless steel rack version |
|---|---|---|
| Wetted material | Brass body, globe or ball trim | Stainless steel, positioned as an alternative to brass |
| Size range | DN15 to DN50 threaded; DN65 to DN150 flanged | Not published |
| Nominal flow | 1.5 to 18 m³/h threaded; 30 to 170 m³/h flanged | Not published |
| Connections | ISO-228 external thread; ISO-7005 flange | Tri-clamp, standard to high-flow |
| Flow measurement | Ultrasonic, ±2% water, ±6% water-glycol | Flow measured continuously; accuracy not published |
| Temperature measurement | Paired Pt1000 immersion sensors | Temperature measured continuously; sensor type not published |
| Other measured values | Position and power, with cumulative energy storage | Position and power listed on the product page |
| Communication | BACnet IP and Modbus RTU, plus 0/2 to 10 V or 4 to 20 mA analog | "Open communication interfaces"; BACnet IP named on the product page |
| Compliance | Not stated in the datasheet | ASHRAE TC99 and OCP specifications |
| Energy claim | Up to 25% reduction for HVAC applications | No percentage claim in the release |
Do the chip-level and second-level claims hold up?
Neither phrase is Siemens wording. The release describes direct-to-chip rack loop cooling, meaning cold plates sit on the chips while the valve controls the rack loop, and it claims automatic adaptation when racks change rather than second-level balancing. No response time is published, so any second-level figure is an inference, not a specification.
"Direct-to-chip" is an architecture label: coolant is delivered to cold plates mounted on processors and memory rather than to the air stream or a room-level heat exchanger. The valve in this release sits in the rack loop that feeds those plates, upstream of the cold plates themselves. It does not mount on a chip, and the release does not describe chip-level sensing.
"Adaptive" is supported; "second-level" is not. Siemens says the valve adapts automatically when servers or racks are added, removed or replaced, and that local loops reduce dependence on the CDU controller. Neither the press release nor the product page gives a settling time, sampling interval or control-loop cycle time. For a design engineer, that is the difference between a marketing phrase and a control specification, and it should be closed with a datasheet question rather than assumed.
What has Siemens not published yet?
Siemens has not published the DN range, actuator model, pressure and temperature ratings, protocol list, flow accuracy, price or availability date for the stainless steel version. These gaps matter because rack loops are usually specified to a pressure class and a connection standard before a valve is ordered.
- Sizes and flow. The release mentions tri-clamp connections from standard to high-flow but gives no nominal diameters or flow coefficients.
- Actuator. The stainless version is described as having integrated control, but no actuator series or torque figure appears in the announcement.
- Protocols. "Open communication interfaces" is the release wording. BACnet IP appears on the product page for the Intelligent Valve generally; Modbus RTU is documented for the HVAC series. Neither is explicitly confirmed for the rack version.
- Ratings and certification. No pressure class, temperature range, leak class or third-party certification number is stated.
- Commercial terms. No price, lead time or first-shipment date.
What does this mean for plant and spares teams?
For spares teams the practical effect is a new wetted-material option inside a familiar control architecture, so the work shifts from control philosophy to part-number and compatibility checks. Plants running Siemens automation should verify material approval, connection type and control integration before substituting a brass valve in a rack loop.
Three checks decide whether a stainless valve drops into an existing loop. First, connection compatibility: a tri-clamp rack valve will not mate with the threaded or flanged joints of a building-HVAC installation, so the manifold has to be reviewed rather than the valve alone. Second, media approval: glycol and propylene glycol mixtures change measurement behaviour, and the wetted-material approval behind the stainless claim should be confirmed against the actual coolant. Third, control integration: if the valve runs local loops independently of the CDU controller, the point list and alarm mapping in the monitoring layer need to be updated, not just the valve tag.
For maintenance planning, the surrounding instrumentation is the part that usually lags a valve change. Valve position feedback and positioner hardware, analog input cards that carry flow and temperature signals, and fieldbus interfaces connecting the skid to the plant network all have to match the new device. Spares that cover those layers on this site include the Siemens SIMATIC automation spares range, the ET 200S PROFIBUS DP interface module and the SM 331 16-bit analog input module.
Where a loop still uses a conventional pneumatically or electrically actuated valve, the positioner is the component that determines how accurately the flow setpoint is followed: the ABB TZIDC digital valve positioner and the GE Nexus MVP50 valve position control module are the two common routes. Turbine and compressor auxiliary loops that share the same plant network are monitored through the 3500 machinery protection system spares, and steam-side valve and case expansion signals are handled by modules such as the AMS 6500 valve and case expansion module.
For readers tracking Siemens' wider industrial commitments in the region, the company's 2026 procurement letter of intent with Sinopec covers electrical and automation products and equipment standardisation.
Frequently asked questions
Can the stainless steel valve replace a brass Intelligent Valve in an existing rack loop?
Only after three checks. The rack version uses tri-clamp connections rather than the ISO-228 thread or ISO-7005 flange of the building-HVAC series, so the manifold has to change. Siemens has not published a cross-reference table between the brass and stainless variants, and it has not confirmed that the protocol support documented for the HVAC series carries over unchanged. Confirm the wetted-material approval, the connection standard and the point list with Siemens before substituting.
Does the stainless steel version support BACnet IP and Modbus RTU?
The release says only that the valve has open communication interfaces. Siemens' product page for the Intelligent Valve names BACnet IP, and the ACVATIX datasheet documents BACnet IP and Modbus RTU plus 0/2 to 10 V or 4 to 20 mA analog integration for the building version. None of those sources states explicitly that the stainless rack version ships with the same protocol stack, so it has to be confirmed in the order specification.
Is the up-to-25% energy saving figure valid for AI rack loops?
No. That figure appears in Siemens' general Intelligent Valve material for HVAC applications, where the valve balances hydronic circuits and stabilises return temperatures. The 11 November release about the stainless steel rack version makes no percentage energy claim, and the savings in a direct-to-chip loop depend on pump strategy, CDU control and load profile, so the HVAC figure should not be quoted for data center cooling.
Sources
- Siemens press release: Siemens' new stainless steel valve expands liquid cooling offering for AI data centers, 11 November 2026 (HQSIPR202610307483EN)
- WebWire: Siemens' new stainless steel valve expands liquid cooling offering for AI data centers
- Siemens: Intelligent Valve product page, including the rack control version, ASHRAE TC99 and OCP compliance, PG25 compatibility and tri-clamp connections
- Siemens ACVATIX Intelligent Valve EVG/EVF datasheet A6V11444716, 5 May 2025
- Siemens Blog: From Intelligent Valve to Digital Twin, engineering liquid cooling for AI data centers, 6 November 2026