FX1S-10MR-001 | Mitsubishi 6 Input 4 Relay Output PLC





Introduction:
The Mitsubishi FX1S-10MR-001 is a compact PLC with 6 sink inputs, 4 relay outputs, and AC 100–240 V supply, built for demanding oil and gas control panels.
Customer Reviews
UBEST Automation – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
Product Attributes:
Notice: For real-time prices and inventory, please click the button below to contact us.
The Mitsubishi FX1S-10MR-001 is a Relay symbol method + step ladder method for industrial control and automation applications.
Mitsubishi FX1S-10MR-001 is a compact programmable logic controller from the FX1S series, offering 6 sink input points and 4 relay output points on a single base unit. It operates from an AC 100 to 240 V supply and includes a 24 VDC service power supply rated at 400 mA. The controller is engineered for harsh oil and gas environments, where dependable control of small process skids and safety interlocks is mission-critical.
What makes this relay suitable for industrial control panels?
this relay combines a stored program iterative calculation method with interrupt instruction support, delivering deterministic scan behavior for time-sensitive tasks. Its arithmetic processing speed for basic instructions is 0.55 to 0.7 μs per instruction, which keeps response times tight in relay-intensive logic. The unit provides 85 application instructions and 27 sequence instructions, giving engineers flexibility for counting, timing, and comparison functions without adding external hardware.
Relay output contacts are rated for external power supply up to AC 250 V or DC 30 V, with a maximum resistive load of 2 A per output and 8 A per COM terminal. This makes the controller directly compatible with small solenoids, indicator lamps, and interposing relays commonly found in field panels. The mechanical insulation between output circuits and the photocoupler-insulated inputs help isolate field wiring from the logic side, a practical advantage in electrically noisy oilfield installations.

Key technical specifications
- Input voltage: AC 100 to 240 V, with voltage tolerance range AC 85 to 264 V.
- Rated frequency: 50/60 Hz.
- Power consumption: 19 W, including input current.
- 24 VDC service power supply: 400 mA.
- Operating temperature: 0 to 55 °C; storage range -20 to 70 °C.
- Relative humidity: 35 to 85% RH (noncondensing) during operation.
- Input points: 6 sink inputs, DC 24 V ± 10%, 7 mA per point at 24 VDC.
- Output points: 4 relay outputs, 2 A resistive load per output.
- Program memory: 2000-step EEPROM, no memory backup required.
- Clock function: Built-in real-time clock with 1980 to 2079 range and leap year correction.
How does this relay handle power disturbances in oil and gas fields?
Field power in oil and gas facilities is rarely clean. This relay continues operation through instantaneous blackouts of 10 ms or less, which helps avoid nuisance trips during generator transfers or breaker reclosing. The power supply fuse is rated 250 V 1 A, and inrush current is limited to a maximum of 15 A for 5 ms at AC 100 V or 25 A for 5 ms at AC 200 V. These characteristics support stable startup on weak or shared supplies.
For wiring, the unit requires Class D grounding with a grounding resistance of 100 Ω or less, using dedicated or common ground. The input circuit is photocoupler-insulated, and the output circuit uses mechanical insulation, which reduces cross-talk between field signals and logic. The input response time is approximately 10 ms, with a built-in digital filter adjustable from 0 to 15 ms in 1 ms units via D8020. When set to 0, X000 and X001 respond in 10 μs, and X002 to X017 in 50 μs; for this relay, the applicable range is X000 to X005.

Installation and environmental considerations
Mount the controller in a location free of corrosive gases, flammable gas, and serious conductive dust. The operating altitude must not exceed 2,000 m under atmospheric pressure. Vibration resistance depends on mounting method: on DIN rail, the unit withstands 10 to 57 Hz at 0.035 mm amplitude and 57 to 150 Hz at 4.9 m/s² acceleration, tested per IEC 61131-2. Direct installation raises these limits to 0.075 mm amplitude and 9.8 m/s² acceleration. Impact resistance is 147 m/s² for 11 ms, tested three times in each axis.
Withstand voltage tests should follow the datasheet values: AC 1.5 kV for 1 minute between the AC power supply terminal and earth, 500 VAC for 1 minute between the 24 VDC service supply and input terminals and earth, and AC 1.5 kV for 1 minute between relay output terminals and earth. Insulation resistance is 5 MΩ or more at 500 VDC for the power and output circuits, and 500 MΩ or more at 500 VDC for the 24 VDC service supply and input circuits.
Frequently Asked Questions
What is the input voltage range of the Mitsubishi FX1S-10MR-001?
The Mitsubishi FX1S-10MR-001 operates from an AC 100 to 240 V supply with a voltage tolerance range of AC 85 to 264 V at 50/60 Hz.
How many I/O points does the FX1S-10MR-001 provide?
The Mitsubishi FX1S-10MR-001 provides 6 sink input points and 4 relay output points. These points are fixed and cannot be expanded.
Can the FX1S-10MR-001 be used in high-temperature oil and gas environments?
The Mitsubishi FX1S-10MR-001 operates within an ambient temperature range of 0 to 55 °C. Storage temperature range is -20 to 70 °C.
What is the power consumption of the FX1S-10MR-001?
The Mitsubishi FX1S-10MR-001 consumes 19 W, including input current, and provides a 24 VDC service power supply rated at 400 mA.
Is the FX1S-10MR-001 suitable for circuit breaker panel replacement?
The Mitsubishi FX1S-10MR-001 offers relay outputs rated for AC 250 V or DC 30 V, making it suitable for circuit breaker panel replacement where direct switching of interposing relays is required.
Why choose this controller for circuit breaker replacement industrial projects?
When upgrading older relay logic or replacing failed control components, this relay offers a compact footprint and a fixed I/O count that simplifies circuit breaker replacement industrial retrofits. Its relay outputs can directly switch interposing relays or small contactors, reducing the need for additional interface hardware. The 2000-step EEPROM memory holds the program without a battery, which lowers maintenance effort in remote wellhead panels. For mccb replacement projects, the controller's 85 application instructions and high-speed counter functions support timing and counting tasks often associated with motor control centers.
The built-in real-time clock, accurate to ±45 seconds per month at 25 °C, enables time-stamped event logging when paired with an HMI or data logger. Program changes are possible during RUN, and a password protection function helps safeguard logic from unauthorized edits. These features make this relay a practical choice for dependable control in demanding environments.
Buyer's guide: evaluating this relay for your application
Start by confirming the I/O count: 6 inputs and 4 relay outputs are fixed and cannot be expanded. Verify that your signal types match the sink input configuration and that relay output loads stay within 2 A per point. Check the supply voltage against your panel: the unit accepts AC 100 to 240 V, 50/60 Hz. Ensure the ambient temperature during operation stays between 0 and 55 °C. For programming, the relay symbol method and step ladder method are supported, and the 2000-step memory is sufficient for many small process control sequences. If your logic requires more steps, note that the FX1S can only use 2000 steps even with the optional FX1N-EEPROM-8L memory cassette.
Contact PetroPartsOnline for parts suited to your application's requirements.
{"@context": "https://schema.org", "@graph": [{"@type": "Product", "name": "FX1S-10MR-001 | Mitsubishi 6 Input 4 Relay Output PLC", "mpn": "FX1S-10MR-001", "sku": "FX1S-10MR-001", "brand": {"@type": "Brand", "name": "Mitsubishi"}, "description": "The Mitsubishi FX1S-10MR-001 is a Relay symbol method + step ladder method for industrial control and automation applications. Mitsubishi FX1S-10MR-001 is a compact programmable logic controller from the FX1S series, offering 6 sink input points and 4 relay output points on a single base unit. It operates from an AC 100 to 240 V supply and includes a 24 VDC service power supply rated at 400 mA. The controller is engineered for harsh oil and gas environments, where dependable control of small pro", "image": ["https://www.petropartsonline.com/wp-content/uploads/2026/05/FX1S-10MR-001_2.jpg", "https://www.petropartsonline.com/wp-content/uploads/2026/05/FX1S-10MR-001_3.jpg", "https://www.petropartsonline.com/wp-content/uploads/2026/05/FX1S-10MR-001_.jpg", "https://www.petropartsonline.com/wp-content/uploads/2026/05/FX1S-10MR-001_-1.jpg", "https://www.petropartsonline.com/wp-content/uploads/2026/05/FX1S-10MR-001_2-1.jpg"], "category": "I/O Modules"}, {"@type": "FAQPage", "mainEntity": [{"@type": "Question", "name": "How many I/O points does the FX1S-10MR-001 provide?", "acceptedAnswer": {"@type": "Answer", "text": "The Mitsubishi FX1S-10MR-001 provides 6 sink input points and 4 relay output points. These points are fixed and cannot be expanded."}}, {"@type": "Question", "name": "Can the FX1S-10MR-001 be used in high-temperature oil and gas environments?", "acceptedAnswer": {"@type": "Answer", "text": "The Mitsubishi FX1S-10MR-001 operates within an ambient temperature range of 0 to 55 °C. Storage temperature range is -20 to 70 °C."}}, {"@type": "Question", "name": "What is the power consumption of the FX1S-10MR-001?", "acceptedAnswer": {"@type": "Answer", "text": "The Mitsubishi FX1S-10MR-001 consumes 19 W, including input current, and provides a 24 VDC service power supply rated at 400 mA."}}, {"@type": "Question", "name": "Is the FX1S-10MR-001 suitable for circuit breaker panel replacement?", "acceptedAnswer": {"@type": "Answer", "text": "The Mitsubishi FX1S-10MR-001 offers relay outputs rated for AC 250 V or DC 30 V, making it suitable for circuit breaker panel replacement where direct switching of interposing relays is required."}}, {"@type": "Question", "name": "Why choose this controller for circuit breaker replacement industrial projects?", "acceptedAnswer": {"@type": "Answer", "text": "When upgrading older relay logic or replacing failed control components, this relay offers a compact footprint and a fixed I/O count that simplifies circuit breaker replacement industrial retrofits. Its relay outputs can directly switch interposing relays or small contactors, reducing the need for additional interface hardware. The 2000-step EEPROM memory holds the program without a battery, which lowers maintenance effort in remote wellhead panels. For mccb replacement projects, the controller's 85 application instructions and high-speed counter functions support timing and counting tasks often associated with motor control centers. The built-in real-time clock, accurate to ±45 seconds per month at 25 °C, enables time-stamped event logging when paired with an HMI or data logger. Program changes are possible during RUN, and a password protection function helps safeguard logic from unauthorized edits. These features make this relay a practical choice for dependable control in demanding environments. Buyer's guide: evaluating this relay for your application Start by confirming the I/O count: 6 inputs and 4 relay outputs are fixed and cannot be expanded. Verify that your signal types match the sink input configuration and that relay output loads stay within 2 A per point. Check the supply voltage against your panel: the unit accepts AC 100 to 240 V, 50/60 Hz. Ensure the ambient temperature during operation stays between 0 and 55 °C. For programming, the relay symbol method and step ladder method are supported, and the 2000-step memory is sufficient for many small process control sequences. If your logic requires more steps, note that the FX1S can only use 2000 steps even with the optional FX1N-EEPROM-8L memory cassette. Contact PetroPartsOnline for parts suited to your application's requirements."}}]}]}