22A-V6P0H204 | Allen-Bradley 1.1 kW AC Drive, 120V



Introduction:
The Allen-Bradley 22A-V6P0H204 is a PowerFlex 4 AC drive with 1.1 kW output, 120V single-phase input, and an integral RS-485 DSI port for dependable motor control.
Customer Reviews
UBEST Automation – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
Product Attributes:
Notice: For real-time prices and inventory, please click the button below to contact us.
The Allen-Bradley 22A-V6P0H204 is a AC adjustable-frequency drive — PowerFlex 4 for industrial control and automation applications.
The Allen-Bradley 22A-V6P0H204 is a PowerFlex 4 AC adjustable-frequency drive rated 1.1 kW (1.5 HP) with a 100…120V AC single-phase input and 6 A continuous output. It is a replacement plate drive in an IP20 open enclosure, built for panel builders and maintenance teams who need a compact, field-proven variable-speed solution.
For decades, oil and gas operators relied on fixed-speed motors and mechanical throttling to move product through pumps, fans and conveyors. Those methods wasted energy and added wear. Adjustable-frequency drives changed that equation, letting a motor run only as fast as the process demands. The PowerFlex 4 family carried that shift into smaller, mission-critical applications, and this drive continues it with a fixed keypad, LED display and a built-in RS-485 port.
What are the key specifications of this drive drive?
- Rated output power: 1.1 kW (1.5 HP) at 6 A continuous output current.
- Input voltage: 100…120V AC, 1-phase, with ±10 % tolerance and a 90…126V AC range.
- Input frequency: 50/60 Hz supply.
- Output voltage: 0…230V, three-phase.
- Output frequency: 0…240 Hz, programmable.
- Carrier frequency: 2…16 kHz, with the rating based on 4 kHz.
- Efficiency: 97.5 % typical.
- Operating temperature: -10…+50 °C for IP20 open type; -10…+40 °C for IP30/NEMA 1.
- Storage temperature: -40…+85 °C.
- Enclosure: Replacement Plate Drive, IP20 / NEMA/UL Type Open; Frame B.
- Communication: Built-in RS-485 DSI port supporting Modbus RTU.
- Braking: Integral brake IGBT; external resistor minimum 60 Ω (AK-R2-091P500).
These ratings come from the manufacturer's published data for this catalog number. The drive delivers 150 % overload for 60 s and 200 % for 3 s, which helps it ride through brief process surges without tripping.

How does the drive handle harsh conditions and power disturbances?
The operating temperature range of -10…+50 °C for the open type suits many indoor industrial cabinets, while the storage range of -40…+85 °C allows for shipping and standby in unheated spaces. Relative humidity up to 95 % non-condensing is permitted. The drive is tested for 15 g shock and 1 g vibration from 5…2000 Hz during operation, so it can tolerate the mechanical stress common on skids and packaged equipment.
Power quality matters in oil and gas facilities. This drive provides 100 ms faultless power ride-through and a logic control ride-through of 0.5 s minimum (2 s typical). Its DC bus trips at 405 V DC overvoltage and 210 V DC undervoltage, protecting the output stage. Overcurrent protection is set at 200 % hardware limit and 300 % instantaneous fault. These features are built for demanding environments where voltage sags and load swings are routine.
Where is this AC drive typically used?
With its 1.1 kW rating and 120V single-phase input, the drive fits small pumps, fans, mixers and conveyors. In oil and gas service, it can control a chemical dosing pump or a ventilation fan in a control room or analyzer shelter. The RS-485 DSI port allows multi-drop Modbus RTU networking, so several drives can report status to a supervisory system without extra option cards. The integral brake IGBT supports stopping profiles that need dynamic braking when an external resistor is added.
Because the enclosure is open type, the drive must be installed inside a protective cabinet. An optional kit 22-JBAB raises the rating to IP30 / NEMA 1 for field mounting. The drive is convection cooled at the 0.2 kW rating, but this 1.1 kW model is fan cooled, so keep the heatsink clear and verify airflow inside the enclosure.

How should the drive be integrated and maintained?
Wiring follows the published terminal layout. Digital inputs accept 18…24V DC in SRC mode or 0…6V DC in SNK mode, and one analog input is DIP-selectable for 0…10V DC or 4…20 mA. A single Form C relay output is programmable. For Modbus RTU, set node address A104 between 1 and 247, baud rate A103 from 1200 to 38400 bit/s, and format A107 to RTU 8-N-1. RS-485 repeaters may be needed beyond 32 nodes.
Periodic maintenance should include inspecting the heatsink for dust, checking fan operation, and verifying terminal torque. Because the drive is convection cooled only at the lowest power rating, this fan-cooled unit needs clean airflow to stay within its -10…+50 °C ambient limit. Store the drive away from corrosive atmospheres when not installed. For parts suited to your application's requirements, contact PetroPartsOnline.
Frequently asked questions
What is the input voltage of the Allen-Bradley this drive?
The Allen-Bradley this drive accepts a 100…120V AC single-phase input with ±10 % tolerance, corresponding to a 90…126V AC range at 50/60 Hz.
Does this drive include an EMC filter?
No, the Allen-Bradley this drive is supplied without an integral EMC filter. An external L-type filter 22-RF025-CL is published for this rating when CE compliance is required.
What is the operating temperature range of this drive?
The Allen-Bradley this drive operates from -10…+50 °C in its IP20 open-type enclosure. With the optional IP30/NEMA 1 kit, the upper limit is -10…+40 °C.
Can this drive be networked over Modbus RTU?
Yes, the Allen-Bradley this drive has a built-in RS-485 DSI port that supports Modbus RTU function codes 03, 06 and 16, with node addresses from 1 to 247 and baud rates up to 38400 bit/s.
What overload capability does the drive provide?
The Allen-Bradley this drive delivers 150 % of rated output current for 60 s and 200 % for 3 s, supporting short-term process surges without nuisance trips.
Frequently Asked Questions
What is the input voltage of the Allen-Bradley 22A-V6P0H204?
The Allen-Bradley 22A-V6P0H204 accepts a 100…120V AC single-phase input with ±10 % tolerance, corresponding to a 90…126V AC range at 50/60 Hz.
Does the 22A-V6P0H204 include an EMC filter?
No, the Allen-Bradley 22A-V6P0H204 is supplied without an integral EMC filter. An external L-type filter 22-RF025-CL is published for this rating when CE compliance is required.
What is the operating temperature range of this drive?
The Allen-Bradley 22A-V6P0H204 operates from -10…+50 °C in its IP20 open-type enclosure. With the optional IP30/NEMA 1 kit, the upper limit is -10…+40 °C.
Can the 22A-V6P0H204 be networked over Modbus RTU?
Yes, the Allen-Bradley 22A-V6P0H204 has a built-in RS-485 DSI port that supports Modbus RTU function codes 03, 06 and 16, with node addresses from 1 to 247 and baud rates up to 38400 bit/s.
What overload capability does the drive provide?
The Allen-Bradley 22A-V6P0H204 delivers 150 % of rated output current for 60 s and 200 % for 3 s, supporting short-term process surges without nuisance trips.