22A-B017H204 | Allen-Bradley 3.7 kW 200-240V AC Drive



Introduction:
The Allen-Bradley 22A-B017H204 PowerFlex 4 drive delivers 3.7 kW at 17.5 A with RS-485 DSI and IP20 open enclosure for rugged industrial control.
Customer Reviews
UBEST Automation – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
Product Attributes:
Notice: For real-time prices and inventory, please click the button below to contact us.
The Allen-Bradley 22A-B017H204 is a AC adjustable-frequency drive — PowerFlex 4 for industrial control and automation applications.
The Allen-Bradley 22A-B017H204 is a PowerFlex 4 AC adjustable-frequency drive rated 3.7 kW (5 HP) at 17.5 A continuous output, with a 200…240V AC three-phase input and a built-in RS-485 DSI port. This replacement-plate model (IP20 / NEMA/UL Type Open) is engineered for demanding environments where dependable motor speed control is mission-critical.
What makes this drive suitable for oil and gas duty?
The drive combines a rugged open-frame design with a wide operating temperature window and field-proven protective features. Its convection and fan cooling paths, integral brake IGBT, and Modbus RTU capability over RS-485 make it a practical choice for pumps, fans, and conveyors in process areas.
Key technical parameters include:
- Operating temperature: -10…+50 °C for IP20/Open Type; -10…+40 °C for IP30/NEMA 1/UL Type 1.
- Input voltage: 200…240V AC, 3-phase, ±10 % tolerance, 50/60 Hz supply.
- Power supply: 8.6 kVA at 21.0 A input current at rated output; branch fuse 30 A.
- Output: 0…230V three-phase, 0…240 Hz programmable, 17.5 A continuous.
- Overload: 150 % for 60 s, 200 % for 3 s with Class 10 I2t motor protection.
- Efficiency: 97.5 % typical.
- Communication: RS-485 DSI port supporting Modbus RTU (function codes 03, 06, 16).
- Enclosure: IP20 / NEMA/UL Type Open; IP30 kit 22-JBAB available separately.

How does the drive handle harsh electrical conditions?
Power quality in oil and gas facilities can be unpredictable. This drive provides 100 ms faultless power ride-through and 0.5 s minimum logic control ride-through, helping the drive bridge short supply disturbances without tripping. DC bus overvoltage trips at 405 V DC and undervoltage at 210 V DC, while overcurrent protection limits hardware current to 200 % and trips at 300 % instantaneous fault.
The drive meets EN 61000-3-2 harmonic requirements without external mitigation and carries cULus Listing to UL 508C and CSA C22.2 No. 14, along with CE marking to EN 61800-3 and EN 61800-5-1.

Where is this drive typically applied?
Typical installations include variable-torque loads such as centrifugal pumps, cooling-tower fans, and positive-displacement conveyors. The programmable 0…240 Hz output and two independent accel/decel times (0…600 s) allow operators to match ramp profiles to process needs. For remote monitoring, the built-in RS-485 port supports multi-drop Modbus RTU networks with node addresses 1…247 and baud rates up to 38400 bit/s.
Because the drive has no integral EMC filter, CE-compliant installations require an external filter such as the 22-RF021-BS or 22-RF021-BL. Dynamic braking is supported via the integral brake IGBT with an external resistor (minimum 32 Ω, catalog AK-R2-047P500 rated for 5 % duty cycle).
What should engineers know about installation and maintenance?
Mount the drive in an area free of volatile or corrosive gas, vapors, or dust. Maintain clearance for convection or fan cooling, and respect the altitude limit of 1000 m without derating. Periodic inspection should include heatsink cleaning, terminal torque checks, and verification of the RS-485 wiring. The fixed LED keypad provides local diagnostics, while the DSI port enables drive configuration and monitoring through connected peripherals.
For parts suited to your application's requirements, contact PetroPartsOnline.
Frequently Asked Questions
What is the input voltage range of the Allen-Bradley 22A-B017H204?
The Allen-Bradley 22A-B017H204 accepts a 200…240V AC three-phase input with ±10 % tolerance and a 50/60 Hz supply. Its published input voltage range is 180…265V AC, 3-phase.
Does the 22A-B017H204 support Modbus communication?
Yes, the Allen-Bradley 22A-B017H204 includes a built-in RS-485 DSI port that supports Modbus RTU with function codes 03, 06, and 16. Node addresses range from 1 to 247, and baud rates are selectable from 1200 to 38400 bit/s.
What is the operating temperature for this drive?
The Allen-Bradley 22A-B017H204 operates from -10…+50 °C in IP20/Open Type configuration. With the optional IP30/NEMA 1 kit, the upper limit is -10…+40 °C.
Is an external EMC filter required for CE compliance?
Yes, the Allen-Bradley 22A-B017H204 has no integral EMC filter. CE-compliant installations require an external filter such as the 22-RF021-BS or 22-RF021-BL, as published in the drive manual.
What is the continuous output current rating?
The Allen-Bradley 22A-B017H204 delivers 17.5 A continuous output current at 3.7 kW (5 HP). It provides 150 % overload for 60 seconds and 200 % for 3 seconds.