AAV141 vs AAV144 Yokogawa Voltage Input Modules: Non-Isolated vs Isolated 1-5 V Cards

TL;DR: The AAV141 is Yokogawa's 16-channel non-isolated 1–5 V voltage input card for CENTUM VP FIO nodes, while the AAV144 is its isolated counterpart, adding group-switched −10–+10 V bipolar measurement, ±30 V allowed input, and 1500 V AC channel-to-system withstand; pick the AAV141 for common-reference signals and the AAV144 when isolation or bipolar range matters.
Why does isolation separate the AAV141 from the AAV144?
Isolation is the defining difference: the AAV141 is a non-isolated differential voltage input card whose channels share a common reference and tolerate only ±1 V of common-mode voltage, whereas the AAV144 provides channel-to-system isolation rated at 1500 V AC for one minute, letting field devices at different ground potentials share one module safely.
- AAV141: allowed input ±7.5 V with common-mode voltage held within ±1 V; input resistance at least 1 MΩ with power on and at least 340 kΩ with power off (Yokogawa GS 33K50F60-50E Release 5).
- AAV144: input-to-system withstand voltage 1500 V AC for 1 minute, derated to 500 V AC when signals arrive through the KS1 dedicated cable (Yokogawa GS 33K50F60-50E Release 5).
- Both modules support dual redundancy, and neither provides HART communication (Yokogawa GS 33K50F60-50E Release 5).
For a common-ground installation where all sixteen transmitters share the node reference, the AAV141-S50 1–5 V input module covers the full card with a single KS cable.
When should you specify the AAV144 instead of the AAV141?
Specify the AAV144 when field wiring crosses ground-potential differences, when your points need the −10–+10 V bipolar range, or when your design standard mandates isolated terminals; the AAV141 remains the simpler choice for 1–5 V signals already referenced to the node, since both cards update data every 10 ms and weigh 0.2 kg.
- AAV144 ranges are 1–5 V DC and −10–+10 V DC, switched for channels CH1–CH16 as one group rather than per channel (Yokogawa GS 33K50F60-50E Release 5).
- Accuracy is ±4 mV on the 1–5 V range and ±20 mV on the −10–+10 V range (Yokogawa GS 33K50F60-50E Release 5).
- The AAV141 covers 1–5 V DC only; among non-isolated cards, the −10–+10 V bipolar range belongs to the AAV142 (Yokogawa GS 33K50F60-50E Release 5).
For isolated installations, the AAV144-S50 isolated voltage input module terminates on pressure clamp terminals, a MIL connector cable, or the KS1 dedicated cable.
How do AAV141 and AAV144 specifications compare side by side?
Both cards are 16-channel CENTUM VP FIO voltage input modules that update data every 10 ms, hold ±4 mV accuracy on the 1–5 V range, support dual redundancy, and weigh 0.2 kg; the table below contrasts only the parameters that differ, taken from GS 33K50F60-50E Release 5.
| Parameter | AAV141 | AAV144 |
|---|---|---|
| Isolation | Non-isolated differential input | Isolated between input and system |
| Measurement range | 1–5 V DC | 1–5 V DC or −10–+10 V DC (CH1–CH16 switched as one group) |
| Allowed input voltage | ±7.5 V (common mode within ±1 V) | ±30 V |
| Accuracy | ±4 mV | ±4 mV (1–5 V); ±20 mV (−10–+10 V) |
| Input resistance | ≥1 MΩ with power on; ≥340 kΩ with power off | 1 MΩ with power on; 200 kΩ with power off |
| Withstand voltage | None (non-isolated design) | 1500 V AC for 1 minute, input to system; 500 V AC via KS1 dedicated cable |
| External connection | KS cable | Pressure clamp terminals, MIL connector cable, or dedicated cable (KS1) |
- Step response: 100 ms on the AAV141 (Yokogawa GS 33K50F60-50E Release 5).
- Current consumption at 5 V DC: 350 mA for the AAV141 versus 500 mA for the AAV144 (Yokogawa GS 33K50F60-50E Release 5).
- Temperature drift: ±4 mV/10°C on the AAV141 and on the AAV144's 1–5 V range; ±20 mV/10°C on the −10–+10 V range (Yokogawa GS 33K50F60-50E Release 5).
Where do AAV141 and AAV144 modules mount in a CENTUM VP system?
Both voltage input modules install in the I/O slots of ESB bus and ER bus node units — ANB10S/D, ANB11S/D, and ANR10S/D — and in the field control units AFV30/40, AFV10, and AFF50; either card can run in a dual-redundant pair, and neither provides HART communication.
- Suffix codes share one structure on both modules: -S for Standard; second position 5 (non-explosion-protected) or E (explosion-protected); third position 0 (basic type) or 3 (ISA G3 with −20–70°C option) (Yokogawa GS 33K50F60-50E Release 5).
- The /K4A00 suffix designates the KS Cable Interface Adapter (ATK4A-00) (Yokogawa GS 33K50F60-50E Release 5).
- Weight is 0.2 kg per module (Yokogawa GS 33K50F60-50E Release 5).
Which signals belong on AAI143 current input modules instead?
Neither voltage card fits 4–20 mA current loops: voltage modules measure the 1–5 V signal developed across a resistor, so two-wire transmitters should land on a current input module such as the AAI143 — a 16-channel isolated 4–20 mA card with ±16 µA accuracy and HART support — while the AAV141 and AAV144 serve true voltage signals.
- GS 33K50F60-50E Release 5 classifies the AAV141 and AAV144 as voltage input modules; 4–20 mA current signals require a current input module from the same FIO family.
- The AAI143 provides 16 isolated 4–20 mA channels with ±16 µA accuracy and HART support (Yokogawa GS 33K50F60-50E Release 5).
For live two-wire transmitters, specify the AAI143-S50 isolated current input module; our Yokogawa AAI143 current input module guide compares the AAI series in depth.
Frequently asked questions
Are the AAV141 and AAV144 interchangeable in my CENTUM VP node?
Both modules are 16-channel voltage input cards for the same CENTUM VP FIO racks — ESB bus and ER bus node units ANB10S/D, ANB11S/D, and ANR10S/D plus field control units AFV30/40, AFV10, and AFF50 — and both support dual redundancy, but they are not electrical drop-ins: the AAV141 is non-isolated with ±7.5 V allowed input and KS cable termination, while the AAV144 is isolated with ±30 V allowed input and pressure clamp, MIL connector, or KS1 cable termination. A swap also changes range behavior, because the AAV144 can shift all sixteen channels to −10–+10 V as one group while the AAV141 reads 1–5 V DC only. Verify field grounding and termination hardware before substituting either card.
Which module should I order for a mix of 1–5 V and −10–+10 V points?
Order the AAV144, because the −10–+10 V bipolar range is available only on the isolated AAV144 and the non-isolated AAV142 among these cards, while the AAV141 is limited to 1–5 V DC; note that the AAV144 switches its range for channels CH1–CH16 as one group, so all sixteen points on the card must share one range, with ±4 mV accuracy on 1–5 V and ±20 mV on −10–+10 V. If every point is 1–5 V and already shares the node's reference potential, the non-isolated AAV141 is the simpler choice, drawing 350 mA versus 500 mA at 5 V DC. Where wiring crosses ground potentials, the AAV144's 1500 V AC channel-to-system withstand becomes the deciding feature.
What should I check before replacing a failed voltage input card?
Start with the full model and suffix code, because the suffix structure is identical on both cards: -S denotes Standard, the second position is 5 for non-explosion-protected or E for explosion-protected types, the third position is 0 for the basic type or 3 for ISA G3 with the −20–70°C option, and /K4A00 adds the KS Cable Interface Adapter (ATK4A-00), so a mismatched suffix can change explosion protection and cable-interface compatibility. Next, match isolation and termination, because a non-isolated AAV141 on KS cable does not swap directly for an isolated AAV144 on pressure clamp terminals or KS1 cable. Finally, confirm the failed loop is a voltage signal at all, since 4–20 mA current loops belong on current input modules such as the AAI143.
Sourcing note: As an independent distributor of Yokogawa CENTUM VP FIO spares, we supply AAV141, AAV144, and AAI143 modules in the standard and option-coded suffixes described above. We quote against the full model and suffix code you provide, and every specification in this article follows Yokogawa GS 33K50F60-50E Release 5. Send us your node unit type, channel count, and signal ranges, and we will confirm the correct voltage or current input card before you order.