22A-B1P5N104 | Allen-Bradley 0.2 kW PowerFlex 4 AC Drive



Introduction:
Allen-Bradley 22A-B1P5N104 is a 0.2 kW PowerFlex 4 AC drive rated 1.5 A at 200…240V AC three-phase, with an integral brake IGBT and RS-485 DSI port.
Customer Reviews
UBEST Automation – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
Product Attributes:
Notice: For real-time prices and inventory, please click the button below to contact us.
The Allen-Bradley 22A-B1P5N104 is a AC adjustable-frequency drive — PowerFlex 4 for industrial control and automation applications.
Allen-Bradley 22A-B1P5N104 is a PowerFlex 4 AC adjustable-frequency drive rated 0.2 kW (0.25 HP) and 1.5 A continuous output at 200…240V AC three-phase input. It is a panel-mount, IP20 / NEMA/UL Type Open unit in Frame A, built with an integral brake IGBT and a built-in RS-485 DSI port.
What this drive Offers on the Panel
This drive suits engineers sizing a small, dependable variable-speed section where space and wiring simplicity matter. The catalog number decodes cleanly: 22A for the PowerFlex 4 family, B for the 240V AC three-phase voltage class, 1P5 for the 1.5 A rating, N for panel mount, and 0 for the unfiltered emission class.
- Rated output power: 0.2 kW (0.25 HP) at 1.5 A continuous output current.
- Supply voltage: 200…240V AC, 3-phase, with ±10 % input voltage tolerance.
- Input voltage range: 180…265V AC, 3-phase, drawing 1.8 A at rated output.
- Input frequency: 50/60 Hz supply.
- Output frequency: 0…240 Hz, programmable.
- Carrier frequency: 2…16 kHz, with the rating based on 4 kHz.
- Efficiency: 97.5 % typical.
- Power dissipation: 32 W total at rated load, split 16 W external and 16 W internal.
- Enclosure: IP20 / NEMA/UL Type Open, Frame A, panel mount.
The carrier frequency deserves attention. Because the rating is based on 4 kHz, raising parameter A091 above that point trades thermal margin for quieter motor operation. Treat the published 1.5 A as the continuous ceiling at the reference setting.

Operating Temperature and Environmental Limits
Heat is the dominant failure mode in compact drives, so the ambient envelope should drive enclosure design. This drive is rated for -10…+50 °C in IP20/Open Type configuration, dropping to -10…+40 °C if the IP30 / NEMA 1 / UL Type 1 kit 22-JBAA is fitted. Flange and plate mounts publish a heatsink range of -10…+40 °C with the drive at -10…+50 °C.
Storage spans -40…+85 °C, relative humidity is 0…95 % non-condensing, and altitude is 1000 m maximum without derating. The drive tolerates 15 g peak shock for 11 ms and 1 g peak vibration from 5…2000 Hz while operating. Sound pressure is 50 dBA for Frame A at one metre.
One installation constraint is absolute: the ambient atmosphere must not contain volatile or corrosive gas, vapors or dust. In oil and gas service, that means locating the drive in a clean control enclosure rather than at the process.
How Does the Drive Ride Through Supply Disturbances?
Electrical robustness is where this model earns its place in mission-critical panels. A 100 ms faultless power ride-through keeps the motor running through short supply dips, while logic control ride-through is 0.5 s minimum and 2 s typical.
Protection thresholds are published and predictable. The DC bus trips at 405 V DC overvoltage and 210 V DC undervoltage. Overcurrent limits are 200 % hardware and 300 % instantaneous fault, and I2t motor protection provides Class 10 protection with 150 % overload for 60 s and 200 % for 3 s. Branch protection calls for UL Class J, CC, T or Type BS88 fuses, or Bulletin 140M/140MT motor protectors and 100-C/100-E contactors.

Control, I/O and RS-485 Integration
Commissioning is straightforward for a fixed-keypad drive with an LED display. Three dedicated digital inputs cover Stop, Start/Run FWD and Direction/Run REV, with two more programmable at 6 mA. One analog input is DIP-selectable between 0…10V DC and 4…20 mA, and one programmable Form C relay handles status signalling.
Speed regulation is ±2 % of base speed across a 40:1 range with slip compensation. Two independent accel and decel ramps each span 0…600 s in 0.1 s increments, and stop modes include Ramp, Coast, DC-Brake, Ramp-to-Hold and S Curve.
The built-in RS-485 DSI port supports Modbus RTU with function codes 03, 06 and 16. Node address A104 spans 1…247 and baud rate A103 spans 1200…38400 bit/s, defaulting to 9600 with RTU 8-N-1 format. Beyond 32 nodes, RS-485 repeaters may be required. No communication option-card slot is published, so network expansion relies on external kits such as 22-XCOMM-DC-BASE.
Integration note: wiring into a plant network may require an external gateway or connection module. Confirm cable and gateway selection with the supplier before ordering.
Reliability Guidance for Field Service Teams
These drives are rugged and field-proven when the enclosure is right. Inspect heatsink fins and enclosure filters periodically, verify terminal torque, and confirm the ambient stays inside the published band. Because cooling is convection for the 0.2 kW rating, natural airflow around the panel matters more than fan maintenance.
Dynamic braking needs an external resistor; the published minimum is 60 Ω, catalog AK-R2-091P500 rated for a 5 % duty cycle. CE compliance requires an external filter, with the S Type 22-RF9P5-AS and L Type 22-RF9P5-AL published for this rating.
Please note this model is discontinued, with a discontinuation date of 2025-06-30. The engineering replacement published in official product data is 25A-B1P6N104. Contact PetroPartsOnline for parts suited to your application's requirements and to confirm lifecycle status before ordering.
Frequently Asked Questions
What are the input voltage and current ratings of the 22A-B1P5N104?
The Allen-Bradley 22A-B1P5N104 accepts 200…240V AC three-phase supply with ±10 % tolerance, an input voltage range of 180…265V AC, and 50/60 Hz input frequency. Input current is 1.8 A at rated output, with a 0.75 kVA input rating and a 3 A branch fuse.
What operating temperature range does the 22A-B1P5N104 support?
The Allen-Bradley 22A-B1P5N104 is rated -10…+50 °C in IP20/Open Type configuration and -10…+40 °C when the IP30 / NEMA 1 / UL Type 1 kit is fitted. Storage temperature spans -40…+85 °C, and altitude is limited to 1000 m without derating.
Does the 22A-B1P5N104 include an EMC filter or braking capability?
The Allen-Bradley 22A-B1P5N104 ships without an integral EMC filter, so CE compliance requires an external filter; the published options for this rating are the S Type 22-RF9P5-AS and L Type 22-RF9P5-AL. An integral brake IGBT is fitted, but dynamic braking requires an external resistor of at least 60 Ω.
Is the 22A-B1P5N104 still available for new projects?
The Allen-Bradley 22A-B1P5N104 carries a discontinued status in official product data, with a discontinuation date of 2025-06-30. The published engineering replacement is 25A-B1P6N104. Contact PetroPartsOnline to confirm current lifecycle status and availability before specifying it.
What communication interface is built into the 22A-B1P5N104?
The Allen-Bradley 22A-B1P5N104 provides one built-in RS-485 DSI port supporting Modbus RTU function codes 03, 06 and 16. Node addresses span 1…247 and baud rates span 1200…38400 bit/s, defaulting to 9600 with RTU 8-N-1 format. No communication option-card slot is published for this model.