22A-B8P0N104 | Allen-Bradley 8 A 1.5 kW AC Drive



Introduction:
The Allen-Bradley 22A-B8P0N104 is a discontinued PowerFlex 4 AC drive rated 8 A and 1.5 kW, with 200…240V AC three-phase input and integral RS-485 DSI.
Customer Reviews
UBEST Automation – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
Product Attributes:
Notice: For real-time prices and inventory, please click the button below to contact us.
The Allen-Bradley 22A-B8P0N104 is a AC adjustable-frequency drive — PowerFlex 4 for industrial control and automation applications.
The Allen-Bradley 22A-B8P0N104 is a PowerFlex 4 AC adjustable-frequency drive rated 8 A and 1.5 kW (2 HP) with a 200…240V AC three-phase input. It is a panel-mount, IP20 open-type unit with a fixed LED keypad and a built-in RS-485 DSI port. Note that this model is discontinued; the published engineering replacement is 25A-B8P0N104.
What engineering problems does this drive solve?
Legacy panels often need a compact drive that tolerates real plant conditions. This drive addresses several field pain points in one frame. It is built for demanding environments where heat, vibration and electrical noise are routine.
- Operating temperature: -10…+50 °C for the IP20 open type, with -10…+40 °C when the IP30 kit is fitted.
- Input voltage: 200…240V AC three-phase, with an input voltage range of 180…265V AC.
- Power supply tolerance: ±10 % input tolerance and 50/60 Hz supply.
- Continuous output current: 8 A with 1.5 kW (2 HP) rated output power.
- Overload capability: 150 % for 60 s and 200 % for 3 s, published as I2t Class 10 motor protection.
- Efficiency: 97.5 % typical, with 85 W total power dissipation at rated load.
- Enclosure: Panel mount, IP20 / NEMA/UL Type Open; IP30 / NEMA 1 requires field-installed kit 22-JBAA.
- Communication: Built-in RS-485 DSI port supporting Modbus RTU.
These ratings let the drive hold speed under load swings while keeping panel heat manageable. The 100 ms power ride-through and 0.5 s minimum logic ride-through further reduce nuisance trips on unstable supplies.

How does the drive handle harsh oil and gas environments?
Field-proven protection starts with environmental limits. This drive operates from -10…+50 °C in open-type form and stores from -40…+85 °C. It withstands 15 g peak shock for 11 ms and 1 g peak vibration from 5…2000 Hz while operating.
Relative humidity may reach 95 % non-condensing, and altitude is limited to 1000 m without derating. The manual requires an ambient atmosphere free of volatile or corrosive gas, vapors or dust. Therefore, install the drive in a clean enclosure or a controlled room when corrosive vapors are present.
Cooling is by convection only on the smallest ratings; this 1.5 kW frame is fan cooled. Sound pressure is 50 dBA at 1 m, so acoustic impact on the panel area stays modest. For mission-critical skids, these limits support dependable operation when the surrounding process equipment is rugged.

How do you integrate this drive into a control system?
The drive provides three dedicated digital inputs (Stop, Start/Run FWD, Direction/Run REV) plus two programmable inputs. One analog input is DIP-selectable for 0…10V DC or 4…20 mA. A single programmable Form C relay output is rated 3.0 A resistive at 30V DC and 125/240V AC.
For network control, the built-in RS-485 DSI port supports Modbus RTU with function codes 03, 06 and 16. Node address A104 spans 1…247, and baud rate A103 spans 1200…38400 bit/s. The default format is RTU 8-N-1. RS-485 repeaters may be required beyond 32 nodes.
No communication option-card slot is published for the PowerFlex 4. Published accessories include the external DSI communications kit 22-XCOMM-DC-BASE and the 22-RJ45CBL-C20 DSI cable. Integration note: wiring into a plant network may require an external gateway or connection module; confirm cables and gateways with PetroPartsOnline before ordering.
Which maintenance and lifecycle points matter most?
Inspect the heatsink and fan path periodically, because 63 W of the 85 W total loss leaves through the heatsink. Keep the enclosure atmosphere clean, since corrosive vapors and dust are prohibited. Verify terminal torque and motor cable condition during scheduled shutdowns, and follow the manufacturer's safety manual for any work inside the panel.
This model is discontinued, with a discontinuation date of 2025-06-30. The published engineering replacement is 25A-B8P0N104. For existing installations, confirm spares strategy and lifecycle status with PetroPartsOnline before ordering. The drive carries cULus Listing to UL 508C and CSA C22.2 No. 14, CE marking to EN 61800-3 and EN 61800-5-1, and KC registration KCC-REM-RAA-22A.
Contact PetroPartsOnline for parts suited to your application's requirements.
Frequently Asked Questions
What input voltage does the Allen-Bradley 22A-B8P0N104 require?
The Allen-Bradley 22A-B8P0N104 accepts a 200…240V AC three-phase input with ±10 % tolerance. Its published input voltage range is 180…265V AC, and the supply frequency is 50/60 Hz.
What is the operating temperature range of the 22A-B8P0N104?
The 22A-B8P0N104 operates from -10…+50 °C in IP20 open-type form. Fitting the IP30 kit reduces the upper limit to -10…+40 °C, and storage is rated -40…+85 °C.
Is the 22A-B8P0N104 still available?
The 22A-B8P0N104 is discontinued, with a discontinuation date of 2025-06-30. The published engineering replacement is 25A-B8P0N104. Contact PetroPartsOnline to confirm current lifecycle status and availability before ordering.
What communication port does the 22A-B8P0N104 provide?
The 22A-B8P0N104 includes one built-in RS-485 DSI port. It supports Modbus RTU with function codes 03, 06 and 16, node addresses 1…247 and baud rates 1200…38400 bit/s.
How much continuous output current does the 22A-B8P0N104 deliver?
The 22A-B8P0N104 delivers 8 A continuous output current at 1.5 kW (2 HP). It provides 150 % overload for 60 s and 200 % for 3 s, published as I2t Class 10 motor protection.