22A-B4P5N104 | Allen-Bradley 0.75 kW PowerFlex 4 AC Drive



Introduction:
Allen-Bradley 22A-B4P5N104 is a discontinued PowerFlex 4 AC drive rated 0.75 kW with 4.5 A output and 200…240V AC three-phase input for panel mounting.
Customer Reviews
UBEST Automation – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
Product Attributes:
Notice: For real-time prices and inventory, please click the button below to contact us.
The Allen-Bradley 22A-B4P5N104 is a AC adjustable-frequency drive — PowerFlex 4 for industrial control and automation applications.
What the Allen-Bradley 22A-B4P5N104 Delivers in a Panel-Mount Drive
The Allen-Bradley this drive is a PowerFlex 4 AC adjustable-frequency drive with a 0.75 kW (1 HP) rating, 4.5 A continuous output current and a 200…240V AC three-phase input class. It is a fixed-keypad model with an LED display, a built-in RS-485 DSI port and an IP20 / NEMA/UL Type Open enclosure for panel mounting. The drive is listed as discontinued with a discontinuation date of 2025-06-30, and the published engineering replacement is 25A-B5P0N104.

Key Specifications of This PowerFlex 4 Drive
- Rated output power: 0.75 kW (1 HP) at 4.5 A continuous output current.
- Input voltage: 200…240V AC, 3-phase, with ±10 % input voltage tolerance.
- Input voltage range: 180…265V AC, 3-phase, at 50/60 Hz supply.
- Input ratings: 2.25 kVA at 5.2 A input current at rated output, with a 10 A branch fuse.
- Output frequency: 0…240 Hz programmable.
- Carrier (PWM) frequency: 2…16 kHz, with the rating based on 4 kHz.
- Operating temperature: -10…+50 °C for IP20/Open Type; -10…+40 °C for IP30/NEMA 1/UL Type 1.
- Storage temperature: -40…+85 °C.
- Relative humidity: 0…95 % non-condensing.
- Altitude: 1000 m (3300 ft) maximum without derating.
- Efficiency: 97.5 % (typical).
- Power dissipation: 55 W total at rated load, rated speed and the published PWM setting.
- Dimensions (H×W×D): 152.0 × 80.0 × 136.0 mm for the panel-mount drive body.
- Weight: 1.4 kg shipping weight for Frame A.
- Agency certification: cULus Listed to UL 508C and CSA C22.2 No. 14.
The 200…240V AC input class and the 4.5 A output rating define the electrical envelope for this catalog number. At rated load the drive dissipates 55 W in total, split into 35 W external through the heatsink and 20 W internal inside the electronics enclosure. That split matters when panel airflow is planned, because the internal portion stays inside the cabinet.
How the Drive Handles Temperature and Power Quality
Operating temperature is the first limit to check in a panel design. The IP20 / NEMA/UL Type Open rating allows -10…+50 °C surrounding air, while the IP30 / NEMA 1 / UL Type 1 configuration through the field-installed kit 22-JBAA reduces that ceiling to -10…+40 °C. Flange and plate mounts publish a heatsink range of -10…+40 °C and a drive range of -10…+50 °C. Storage temperature extends from -40…+85 °C, so the unit tolerates wide transport swings before installation.
On the power side, the input voltage tolerance of ±10 % covers the published 180…265V AC range for this rating. The DC bus trips at 405 V DC on overvoltage and 210 V DC on undervoltage. Power ride-through is published at 100 ms faultless, and logic control ride-through is 0.5 s minimum and 2 s typical. These figures describe how the drive responds to short supply disturbances rather than to sustained voltage problems.

Control I/O and RS-485 DSI Communications
The control section provides three dedicated digital inputs for Stop, Start/Run FWD and Direction/Run REV, plus two programmable digital inputs. Input current is 6 mA, with SRC mode turning on at 18…24V DC and SNK mode turning on at 0…6V DC. One analog input is DIP-selectable between 0…10V DC at 100 kΩ and 4…20 mA at 250 Ω. A single programmable Form C relay output is rated 3.0 A resistive and 0.5 A inductive at 30V DC, 125V AC and 240V AC.
For networking, the built-in RS-485 DSI port supports Modbus RTU with function codes 03, 06 and 16. Node address A104 spans 1…247, baud rate A103 spans 1200…38400 bit/s with a default of 9600, and format A107 is RTU 8-N-1. Up to two peripherals can attach to a drive. Beyond 32 nodes, RS-485 repeaters may be required. No communication option-card slot is published for the PowerFlex 4; the published accessories include the External DSI Communications Kit 22-XCOMM-DC-BASE and the 22-RJ45CBL-C20 DSI cable.
Why this drive Suits Demanding Panel Environments
This drive is built for demanding environments where vibration and shock are part of normal operation. It is published for 15 g peak shock for 11 ms and 1 g peak vibration across 5…2000 Hz while operating. The atmosphere requirement is equally specific: the drive must not be installed where volatile or corrosive gas, vapors or dust are present, and it must be stored away from a corrosive atmosphere when not installed.
For braking duties, an integral brake IGBT is fitted, and dynamic braking requires an external resistor. The published resistor for this rating is a minimum 60 Ω unit, catalog AK-R2-091P500, rated for a 5 % duty cycle. Motor cable length depends on the EMC arrangement: 10 m in First Environment Restricted Distribution or Second Environment and 1 m in First Environment Unrestricted Distribution with the integral filter or an external S-type filter, and 100 m or 5 m with an external L-type filter. No integral EMC filter is fitted to this catalog number, so CE compliance calls for an external filter such as 22-RF9P5-AS or 22-RF9P5-AL.
Lifecycle Status and Replacement Path
The official product data lists this drive as discontinued, with a discontinuation date of 2025-06-30. The published engineering replacement is 25A-B5P0N104. Sites that still run this catalog number should confirm spares coverage before maintenance windows close. Contact PetroPartsOnline for parts suited to your application's requirements and to verify current lifecycle status and availability before ordering.
Frequently Asked Questions
What input voltage does the 22A-B4P5N104 accept?
The Allen-Bradley 22A-B4P5N104 accepts a 200…240V AC three-phase input with ±10 % tolerance, which corresponds to a published input voltage range of 180…265V AC at 50/60 Hz supply.
What is the operating temperature range of the 22A-B4P5N104?
The Allen-Bradley 22A-B4P5N104 operates from -10…+50 °C in its IP20 / NEMA/UL Type Open enclosure, and from -10…+40 °C when configured as IP30 / NEMA 1 / UL Type 1 with the field-installed kit 22-JBAA.
Is the 22A-B4P5N104 still available?
The Allen-Bradley 22A-B4P5N104 is listed as discontinued with a discontinuation date of 2025-06-30, and the published engineering replacement is 25A-B5P0N104. Contact PetroPartsOnline to verify current availability before ordering.
Does the 22A-B4P5N104 include an EMC filter?
The Allen-Bradley 22A-B4P5N104 has no integral EMC filter, so CE compliance requires an external filter. The published external filters for this rating are the S Type 22-RF9P5-AS and the L Type 22-RF9P5-AL.
What communication port is built into the 22A-B4P5N104?
The Allen-Bradley 22A-B4P5N104 includes one built-in RS-485 DSI port that supports Modbus RTU with function codes 03, 06 and 16, node addresses 1…247 and baud rates from 1200 to 38400 bit/s.