25C-E032N104 | Allen-Bradley 22 kW 525-600V AC Drive



Introduction:
The Allen-Bradley 25C-E032N104 is a PowerFlex 527 AC drive rated 22 kW normal duty with dual EtherNet/IP and integrated safety for rugged oil and gas installations.
Customer Reviews
UBEST Automation – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
Product Attributes:
Notice: For real-time prices and inventory, please click the button below to contact us.
The Allen-Bradley 25C-E032N104 is a AC adjustable-frequency drive — PowerFlex 527 for industrial control and automation applications.
The Allen-Bradley 25C-E032N104 is a PowerFlex 527 AC adjustable-frequency drive rated 22 kW (30 HP) normal duty and 18.5 kW (25 HP) heavy duty at 32 A, with a 525…600V AC three-phase input. It combines a panel-mount IP20 open-type enclosure, dual embedded EtherNet/IP ports, and integrated Safe Torque Off safety in one frame E package built for demanding environments.
What should buyers verify before selecting this drive?
Start with the electrical envelope. The drive accepts 525…600V AC three-phase input with -15 % / +10 % voltage tolerance and 47…63 Hz input frequency. Continuous output current is 32 A maximum at rated output voltage, and output frequency is programmable from 0…590 Hz. Normal duty overload reaches 110 % of rated output current for up to 60 s and 150 % for up to 3 s. Heavy duty overload reaches 150 % for up to 60 s and 180 % for up to 3 s. Efficiency is 97.5 % typical, and displacement power factor is 0.98 across the entire speed range.
Confirm the supply arrangement. Three-phase input provides the full rating, while single-phase input on this three-phase drive provides 35 % of the rating. The maximum short-circuit rating is 100,000 A symmetrical, with the actual rating determined by the installed fuse or circuit breaker. DC bus overvoltage trips at 1005 V DC, and undervoltage trips at 487 V DC. Power ride-through is 100 ms, and logic control ride-through is 0.5 s minimum and 2 s typical.

How does the drive handle harsh oil and gas environments?
Environmental ratings matter on site. Operating temperature for vertical IP20/Open Type mounting is -20…+50 °C without derating, up to +60 °C derated, and up to +70 °C derated with the 25-FANx-70C control module fan kit. The ambient minimum is -20 °C for every mounting method. Storage temperature for Frame E is -40…+70 °C. Relative humidity is 0…95 % non-condensing, and the drive complies with IEC 60721-3-3 level 3C2 for chemical and gases only, so the ambient atmosphere must not contain volatile or corrosive gases, vapors or dust.
Mechanical ruggedness is published for Frame E: 15 g operating shock and 30 g non-operating shock, plus 1.5 g operating vibration and 2.5 g non-operating vibration, both complying with IEC 60068-2-27 and IEC 60068-2-6:2007. Sound pressure level is 68 dBA at 1 m. Altitude is 1000 m maximum without derating, up to 4000 m with derating, except 600V drives limited to 2000 m. These figures support dependable operation where vibration and temperature swings are routine.
Key technical specifications
- Input voltage: 525…600V AC, 3-phase, with -15 % / +10 % tolerance.
- Input frequency: 47…63 Hz.
- Normal duty rating: 22 kW (30 HP) at 32 A continuous output.
- Heavy duty rating: 18.5 kW (25 HP) at 32 A continuous output.
- Output frequency: 0…590 Hz programmable.
- Efficiency: 97.5 % typical.
- Operating temperature: -20…+50 °C without derating, up to +70 °C derated with fan kit.
- Enclosure: IP20 NEMA/Open Type, panel mount, Frame E.
- Communication: dual embedded EtherNet/IP ports.
- Safety: hardwired Safe Torque Off, SIL CL 3, PLe, response time less than 12 ms.

How does this drive integrate with control systems?
The dual embedded EtherNet/IP ports support linear, star and Device Level Ring topologies. CIP Safety allows safety data and standard control data and diagnostics to be transmitted simultaneously over the same network. Integrated motion uses CIP Motion commands with a Logix-based control system. A safety or non-safety ControlLogix controller must also use a 1756-EN2T, 1756-EN2TR or 1756-EN3TR EtherNet/IP module, while a CompactLogix 5370 controller has dual embedded EtherNet/IP ports. The drive is ODVA conformance tested to EtherNet/IP specifications.
Control I/O includes four programmable 24V DC digital inputs, two isolated analog inputs (-10…+10V DC or 4…20 mA, 10-bit), two relay outputs, two opto outputs, and one non-isolated analog output (0…10V or 0…20 mA). An incremental encoder option board, 25-ENC-2, provides 5V or 12V at 250 mA supply. Note that the PowerFlex 527 has no RS-485 DSI port, so DSI accessories such as the 22-SCM-232 are not applicable. For network wiring, confirm cables and any gateway requirements with the supplier.
What safety and certification details matter for compliance?
The integrated Safe Torque Off function is TÜV Rheinland approved up to Performance Level e (PLe), Category 3 according to EN ISO 13849 and SIL CL 3 according to IEC 61508, EN 61800-5-2 and EN 62061. The drive is c-UL-us Listed to UL 508C and CSA C22.2 No. 274, and Listed to UL 61800-5-1 and CSA C22.2 No. 274-17. It carries CE declaration to Low Voltage Directive 2014/35/EU, EMC Directive 2014/30/EU, Machinery Directive 2006/42/EC, RoHS Directive 2011/65/EU and Ecodesign Directive 2009/125/EC. ATEX certification TÜV 15 ATEX 7696 X covers Group II Category (2) GD applications with ATEX approved motors. Lloyd's Register Type Approval Certificate 15/80016(E1) and IEEE P1668 compliance are also published.
Because the drive produces leakage current exceeding 3.5 mA AC and/or 10 mA DC, the earthing conductor must comply with local regulations for high protective-earthing-current equipment. No integral EMC filter is fitted; external filters provide EN 61800-3 Category C1/C2/C3 compliance. The drive is not intended for public low-voltage networks supplying domestic premises without additional mitigation.
What maintenance practices support long service life?
Inspect the cooling fan and heatsink periodically, and keep the enclosure free of dust and corrosive vapors. Verify terminal torque and earthing integrity during scheduled shutdowns. Monitor operating temperature against the derating curve, especially if the 25-FANx-70C fan kit is not installed. The drive is fan cooled, and power dissipation is 562 W total at rated load, rated speed and the PWM setting, so panel ventilation must be adequate. For safety-related functions, follow the manufacturer's safety manual and inspect the STO circuit at recommended intervals.
FAQ
What is the input voltage range of the Allen-Bradley this drive?
The Allen-Bradley this drive accepts 525…600V AC three-phase input with -15 % / +10 % voltage tolerance and 47…63 Hz input frequency.
Can this drive operate at high ambient temperatures?
The Allen-Bradley this drive operates from -20…+50 °C without derating in vertical IP20 mounting, up to +60 °C derated, and up to +70 °C derated with the 25-FANx-70C control module fan kit.
What safety rating does the integrated Safe Torque Off function carry?
The Allen-Bradley this drive Safe Torque Off function is TÜV Rheinland approved up to Performance Level e (PLe), Category 3 according to EN ISO 13849 and SIL CL 3 according to IEC 61508, with a response time less than 12 ms.
Does this drive include an EMC filter?
No, the Allen-Bradley this drive has no integral EMC filter; external filters are required for EN 61800-3 Category C1/C2/C3 compliance.
What communication ports are built into this drive?
The Allen-Bradley this drive provides dual embedded EtherNet/IP ports supporting linear, star and Device Level Ring topologies, and it is ODVA conformance tested to EtherNet/IP specifications.
Contact PetroPartsOnline for parts suited to your application's requirements.