+86 18030005825
No.95, Xiangxing Road, Xiang'an District, Xiamen

140CPU67260 | Schneider Electric Unity Hot Standby Processor

Introduction:

The Schneider Electric 140CPU67260 is a Unity Hot Standby processor for Modicon Quantum, featuring a 266 MHz clock, 3072 kB RAM, and multimode fiber interconnect up to 4 km.

ubest aotomation    Customer Reviews

UBEST Automation – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.

Product Attributes:

Manufacturer: Schneider Electric
Part Number: 140CPU67260
Type: Unity processor
Condition: Subject to stock check
Shipping Port: Xiamen

Notice: For real-time prices and inventory, please click the button below to contact us.

Description
Inquiry

Is your process control architecture resilient enough to tolerate a controller failure without interrupting production? The Schneider Electric 140CPU67260 is a Unity Hot Standby processor for the Modicon Quantum automation platform, built to keep mission-critical operations running through redundant control. It combines a 266 MHz clock frequency with 3072 kB of internal RAM, of which 1536 kB is dedicated to data, and it supports multimode fiber interconnection between primary and secondary PLCs up to 4 km.

Frequently Asked Questions

What is the function of the 140CPU67260 in a Modicon Quantum system?

The Schneider Electric 140CPU67260 is a Unity Hot Standby processor that provides redundant control for Modicon Quantum automation platforms. It uses a multimode fiber optic link to interconnect primary and secondary PLCs up to 4 km.

Can the 140CPU67260 be used for plc cpu module replacement?

Yes, the 140CPU67260 is a Unity processor designed for Modicon Quantum systems. For plc cpu module replacement, confirm compatibility with your existing rack and power budget; the module requires 2760 mA bus current.

What are the memory specifications of the 140CPU67260?

The Schneider Electric 140CPU67260 includes 3072 kB internal RAM, with 1536 kB for data. Program memory is expandable to 7168 kB and file storage to 8 MB using a PCMCIA card.

How does the 140CPU67260 connect to Modbus Plus and Modbus networks?

It provides a SUB-D 9 female connector for the Modbus Plus network and an RJ45 connector for the Modbus bus. These integrated connections support distributed and remote I/O architectures.

What certifications does the 140CPU67260 carry?

The Schneider Electric 140CPU67260 holds CE, CSA, GOST, UL, and Marine certifications. It is also a Green Premium product and RoHS compliant since date code 1111.

How does this controller support Hot Standby redundancy?

Hot Standby redundancy relies on a dedicated link between the primary and secondary controllers. This processor provides one MT-RJ multimode fiber optic connector for interconnecting primary and secondary PLCs up to 4 km, which allows the standby unit to remain synchronized with the primary. The module also includes a key switch for memory port on/off control, giving field personnel a physical means to manage memory access. In addition, local signaling includes one yellow LED for Ethernet activity (COM) and one yellow LED for configuration status (STS), so technicians can verify communication and configuration states at the rack.

Figure 1: Front view of the Schneider Electric 140CPU67260 Unity processor showing its physical design and enclosure.

Key technical specifications

  • Clock frequency: 266 MHz
  • Internal RAM: 3072 kB, with 1536 kB for data
  • Expandable memory: 7168 kB program and 8 MB file storage with PCMCIA card
  • Bus current requirement: 2760 mA
  • Application structure: 1 cyclic/periodic master task and 1 periodic fast task
  • Instruction throughput: 10.28 Kinst/ms if 100 % Boolean; 10.07 Kinst/ms if 65 % Boolean and 35 % numerical
  • System overhead: 1 ms master task; 0.2 ms fast task
  • Integrated connections: 1 Modbus Plus, 1 Modbus, 1 USB, and 1 optic fibre with Hot Standby protocol
  • Electrical connections: RJ45 for Modbus bus; SUB-D 9 female for Modbus Plus network; MT-RJ multimode fiber optic for primary-to-secondary PLC link
  • Product certifications: CE, CSA, GOST, UL, and Marine

The 266 MHz clock and 3072 kB RAM support deterministic execution of control logic in demanding applications. The multimode fiber link up to 4 km separates primary and secondary controllers across plant distances, which is valuable in large oil and gas facilities where control rooms and field racks are far apart.

Where does this Unity processor fit in oil and gas operations?

Oil and gas processes often require continuous operation, and unplanned controller downtime can disrupt upstream and downstream activities. This controller is engineered for harsh oil & gas environments where reliability you can depend on is essential. Its Hot Standby capability supports process control applications that cannot tolerate a single point of failure. The processor handles discrete and analogue I/O across distributed and remote stations, including Modbus Plus networks and Ethernet remote I/O racks. Accurate time stamping and high-speed interrupt inputs are available for application-specific I/O, which helps with event sequencing and diagnostics. For mission-critical operations, this module provides a field-proven foundation for redundant control architectures.

Figure 2: Technical layout and connection details for the Schneider Electric 140CPU67260 Unity processor.

Integration and communication details

The processor includes an Ethernet router communication service and supports up to six optional modules for Ethernet, Modbus, Modbus Plus, Profibus DP, and Sy/Max. Maximum connections include six Ethernet TCP/IP local, six Modbus Plus local, six Profibus DP local, and one Modbus RS232/485 Modbus/ASCII. For Modbus Plus, the SUB-D 9 female connector links the processor to the network. The RJ45 connector handles the Modbus bus. When wiring into these networks, note that integration may require an external gateway or connection module; confirm cables and gateways with PetroPartsOnline for your specific application.

Selection guidance for PLC spare parts

Choosing the right PLC spare parts for a Quantum system requires attention to memory, communication, and redundancy requirements. This controller offers 3072 kB internal RAM and expandability to 7168 kB program memory with a PCMCIA card, which suits applications with growing control logic. Its Hot Standby protocol over fiber provides a robust redundancy path. For plc cpu module replacement projects, verify that the existing rack configuration and power budget can accommodate the 2760 mA bus current requirement. PetroPartsOnline provides application-specific selection guidance to help match this processor to your control architecture.

Reliability and maintenance considerations

In demanding environments, periodic inspection of fiber connectors and network cabling helps maintain signal integrity. The MT-RJ multimode fiber connector should be kept clean and securely seated to preserve the 4 km link between primary and secondary PLCs. Monitor the COM and STS LEDs for early indication of communication or configuration issues. Because the processor is certified for Marine and HazLoc standards, it is suitable for rugged installations, but always follow the manufacturer's safety manual for maintenance procedures. These practices support long-term dependability in mission-critical operations.

Frequently asked questions

What is the function of this controller in a Modicon Quantum system?

The Schneider Electric this controller is a Unity Hot Standby processor that provides redundant control for Modicon Quantum automation platforms. It uses a multimode fiber optic link to interconnect primary and secondary PLCs up to 4 km.

Can this controller be used for plc cpu module replacement?

Yes, this controller is a Unity processor designed for Modicon Quantum systems. For plc cpu module replacement, confirm compatibility with your existing rack and power budget; the module requires 2760 mA bus current.

What are the memory specifications of this controller?

The Schneider Electric this controller includes 3072 kB internal RAM, with 1536 kB for data. Program memory is expandable to 7168 kB and file storage to 8 MB using a PCMCIA card.

How does this controller connect to Modbus Plus and Modbus networks?

It provides a SUB-D 9 female connector for the Modbus Plus network and an RJ45 connector for the Modbus bus. These integrated connections support distributed and remote I/O architectures.

What certifications does this controller carry?

The Schneider Electric this controller holds CE, CSA, GOST, UL, and Marine certifications. It is also a Green Premium product and RoHS compliant since date code 1111.

Contact PetroPartsOnline for parts suited to your application's requirements.

About Ubest

Ubest Automation is a leading global provider of automation products, with deep partnerships with major automation manufacturers to provide customers with customized business solutions, cost-effective products, and comprehensive services.

 

Contact Us

Phone:+86 180 3000 5825

Address:Room 7A, No. 59 Hubin North Road, Siming District Xiamen City China

Email: [email protected]

Contact: Klaus

 

Industry Links

© 2026, Ubest Automation Limited  All Rights Reserved. sitemap