140DAI35300C | Schneider Electric 32-Ch Discrete Input



Introduction:
The 140DAI35300C is a Modicon Quantum discrete input module with 32 channels at 24 V AC, built for demanding oil and gas control cabinets.
Customer Reviews
UBEST Automation – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
Product Attributes:
Notice: For real-time prices and inventory, please click the button below to contact us.
Schneider Electric 140DAI35300C is a discrete input module in the Modicon Quantum series that captures 32 input channels at a nominal 24 V AC. It is a rugged, field-proven choice for mission-critical control cabinets in oil and gas operations where dependable signal acquisition matters.
Why this module Suits Demanding Control Cabinets
Engineers specifying discrete input hardware for harsh environments need predictable electrical behaviour and a clear thermal envelope. This module addresses both concerns with documented parameters rather than assumptions. It requires 2 input words for addressing, so data organization stays compact within the Quantum backplane. Input current sits between 11.1 and 13.2 mA, while maximum leakage current is 1.9 mA. Consequently, field wiring remains easy to validate during commissioning.
Power and thermal planning are equally straightforward. The module draws 250 mA of bus current and dissipates a maximum of 10.9 W. Therefore, enclosure ventilation and backplane loading can be sized with confidence. The ambient temperature range of 0 to 60 °C defines the operating window, so cabinet cooling should keep internal conditions inside that band. The unit weighs 0.34 kg and uses a standard format for straightforward mounting.

Key Features and Technical Specifications
- Input channels: 32 discrete inputs for high-density signal capture.
- Input voltage: 24 V AC nominal supply for AC field signals.
- Input current: 11.1 to 13.2 mA per the published specification.
- Max leakage current: 1.9 mA, supporting dependable off-state detection.
- Addressing requirement: 2 input words within the Quantum system.
- Bus current requirement: 250 mA drawn from the backplane.
- Max power dissipation: 10.9 W for thermal budgeting.
- Ambient temperature: 0 to 60 °C operating range.
- Marking and standards: CE marked; conforms to UL 508 and CSA.
- Weight and format: 0.34 kg in a standard format.
How Does the 24 V AC Input Voltage Simplify Panel Design?
A 24 V AC nominal input lets the module interface with AC field devices commonly found in process areas. Because the input current stays within 11.1 to 13.2 mA, wiring and fusing can be planned around a known load. The 1.9 mA maximum leakage current also helps engineers confirm that off-state signals remain distinguishable. During specification review, these figures remove guesswork from channel-level design.

Integration and Addressing in Modicon Quantum Systems
The module occupies 2 input words, so I/O mapping is defined early in the project. Its 250 mA bus current requirement should be added to the backplane power budget alongside other modules. With a maximum power dissipation of 10.9 W, thermal calculations for the enclosure remain predictable. The standard format supports conventional mounting practice within Quantum racks. Please verify current lifecycle status and availability with PetroPartsOnline before ordering.
Reliability in Oil and Gas Environments
Ambient temperature is a leading cause of premature electronics failure in field cabinets. This module is specified for 0 to 60 °C, so maintaining cabinet conditions inside that window protects long-term operation. Periodic inspection of terminal connections and enclosure filters supports that goal. Combined with the documented leakage and current figures, the design gives maintenance teams measurable baselines for troubleshooting. The result is reliability you can depend on across demanding environments.
Selection Guidance for Project Engineers
When comparing discrete input options, confirm channel count, input voltage and thermal load against your application. This module offers 32 channels at 24 V AC with a 10.9 W maximum dissipation, which suits panels where density and thermal headroom are both planned. Its CE marking and conformity to UL 508 and CSA support specification review. Contact PetroPartsOnline for parts suited to your application's requirements.
Frequently Asked Questions
What input voltage does the 140DAI35300C accept?
The Schneider Electric 140DAI35300C accepts a nominal 24 V AC input voltage across its 32 input channels.
How many input channels does the 140DAI35300C provide?
The 140DAI35300C provides 32 input channels and requires 2 input words for addressing within the Modicon Quantum system.
What is the operating temperature range of the 140DAI35300C?
The module is specified for an ambient temperature range of 0 to 60 °C, so cabinet cooling should keep internal conditions within that band.
What are the power requirements of the 140DAI35300C?
The 140DAI35300C draws 250 mA of bus current and has a maximum power dissipation of 10.9 W.
Which standards and markings apply to the 140DAI35300C?
The Schneider Electric 140DAI35300C carries CE marking and conforms to UL 508 and CSA standards.