HIMA F60CPU03 CPU Module HIMatrix F60 SIL 3
Introduction:
HIMA F60CPU03 Central Module for HIMatrix F60 controller. 4 Ethernet ports, safeethernet, PROFIsafe, SIL 3 certified, 6 ms response time.
Customer Reviews
UBEST Automation – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
Product Attributes:
Notice: For real-time prices and inventory, please click the button below to contact us.
HIMA F60CPU03 Central Processor Module for HIMatrix F60 Controller
Product Overview and Core Function
The HIMA F60CPU03 serves as the central component of the HIMatrix F60 controller. As a result, it stores both the operating system and the user program. Specifically, the module executes all central functions for the safety controller. Consequently, the HIMA F60CPU03 handles communication with PADT and other systems seamlessly.
Slot Location and Physical Integration
The HIMA F60CPU03 can only be inserted in one specific slot location. For instance, this slot is located on the right side next to the power supply module. The module fits directly into the HIMatrix F60 subrack. Therefore, proper slot placement is critical for system operation. In addition, the module monitors operating voltage and temperature continuously.
Ethernet Communication Ports
This CPU module features four Ethernet ports with RJ-45 connectors. Specifically, all ports support 10/100/Base-T transfer standard. Both half duplex and full duplex operation are available. Auto negotiation is supported for simple network integration. In addition, auto crossover eliminates the need for crossover cables. The IP address and subnet mask are freely configurable for network flexibility. Consequently, the HIMA F60CPU03 adapts to various network environments easily.
Supported Safety and Standard Protocols
The HIMA F60CPU03 supports safety-related protocols including safeethernet and PROFIsafe. For standard communication, it supports programming and debugging tool (PADT) protocols. Similarly, OPC, Modbus TCP, TCP SR, and SNTP are available. In addition, ComUserTask and PROFINET are supported for industrial integration. Therefore, this CPU connects to a wide range of devices and systems.
Memory Capacity and Response Time
The total program and data memory for all applications is 5 MB less 64 kBytes for CRCs. Consequently, this provides ample space for complex safety logic. The minimum response time is ≥ 6 ms for reliable safety reactions. Therefore, the HIMA F60CPU03 meets demanding real-time requirements.
Fieldbus Interfaces and Submodules
The module includes two fieldbus interfaces with 9-pole D-sub connectors. Specifically, FB1 and FB2 accept pluggable fieldbus submodules. This design allows flexible fieldbus protocol selection. As a result, you can adapt the HIMA F60CPU03 to various industrial networks. Contact technical support for compatible submodule options.
Power Requirements and Operating Data
The HIMA F60CPU03 requires 24 VDC with -15% to +20% tolerance. The acceptable range is 20.4 V to 28.8 V DC. The residual ripple (rPP) must be ≤ 15% for stable operation. The power supply must provide safe isolation per IEC 61131-2 requirements. The internal operating data includes 3.3 VDC at 1.5 A. In addition, 5 VDC at 0.1 A is required for internal logic.
Time and Date Buffer
A gold capacitor provides buffering for the date and time. Therefore, the HIMA F60CPU03 maintains accurate time during brief power interruptions. This feature supports time-stamped events and diagnostics. Unlike battery-backed modules, gold capacitors require no replacement. Consequently, maintenance is simplified for this CPU module.
Environmental Specifications
The ambient operating temperature range is 0°C to +60°C for normal use. Storage temperature ranges from -40°C to +85°C for transport and storage. The space requirement is 6 RU (rack units) and 4 HP (horizontal pitch). The module weight is only 280 grams for easy handling.
Safety Certifications and Approvals
The HIMA F60CPU03 holds multiple safety certifications for global use. For instance, TÜV certifies compliance with IEC 61508 1-7:2010 up to SIL 3. Similarly, IEC 61511:2004 and EN ISO 13849-1:2008 are fully supported. In addition, IEC 62061:2005, EN 50156-1:2004, and EN 298:2003 apply. EN 230:2005 is also included in the certification scope. The PROFIBUS Nutzerorganisation (PNO) approves the PROFIBUS DP Slave functionality. The CE and EMC markings confirm compliance with European standards.
Installation Guide
Mount the HIMA F60CPU03 in the right slot beside the power supply module. First, ensure the HIMatrix F60 subrack is properly installed and grounded. Insert the module carefully into the designated slot. Connect up to four Ethernet cables to the RJ-45 ports. Configure the IP address and subnet mask for your network. If needed, install fieldbus submodules into FB1 and FB2. Finally, apply 24 VDC power and verify normal operation.
Complete Package Contents
HIMA F60CPU03 Central Processor Module (1 unit)
Four RJ-45 Ethernet ports (10/100/Base-T with integrated switch)
Two 9-pole D-sub fieldbus interfaces (FB1 and FB2)
Gold capacitor for date/time buffering
Operating system pre-installed (user program memory available)
Module housing (6 RU, 4 HP form factor)
Documentation and configuration guide
Frequently Asked Questions (FAQ)
1. What controller does the HIMA F60CPU03 work with?
The HIMA F60CPU03 is the central CPU for the HIMatrix F60 controller. Specifically, it inserts into the slot next to the power supply module.
2. What safety level does this CPU module achieve?
The module is TÜV certified up to SIL 3 according to IEC 61508:2010. Therefore, it suits high-risk safety applications.
3. How many Ethernet ports does the F60CPU03 have?
The module provides four Ethernet ports with RJ-45 connectors. All ports support 10/100/Base-T with auto negotiation.
4. What protocols does the HIMA F60CPU03 support?
Safety protocols include safeethernet and PROFIsafe. Standard protocols include PADT, OPC, Modbus TCP, TCP SR, SNTP, ComUserTask, and PROFINET.
5. What is the response time of this CPU module?
The minimum response time is ≥ 6 ms for safety-critical reactions. Total program memory is 5 MB less 64 kBytes for CRCs.