+86 18030005825
No. 96, Xiangxing Road, Xiang'an District, Xiamen
sales@ubestplc.com

3500/60-01-01 Bently Nevada Temperature Monitor

Introduction:

3500/60-01-01 is a 6-channel temperature monitor for 3500 series racks. It accepts RTD or thermocouple (TC) inputs. This module carries CSA/NRTL/C approval for Class 1, Div 2 areas. It provides recorder outputs and works reliably from -30°C to +65°C. Ideal for bearing and winding temperature monitoring in turbines, compressors, and generators.

ubest aotomation    Customer Reviews

UBEST Automation – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.

Product Attributes:

Manufacturer: Bently Nevada
Series: 3500 Monitoring system
Part Number: 3500/60-01-01
Type: Temperature Monitor
Condition: In Stock
Origin: U.S.A
Weight: 0.91
Shipping Port: Xiamen
Warranty: One year

Notice: For real-time prices and inventory, please click the button below to contact us.

Description
Inquiry

Technical Specifications – Tree View

  • Inputs & Signal Types
    • Accepts 1 to 6 RTD or thermocouple (TC) signals.
    • Input impedance: 10 MΩ for each lead input.
    • Power consumption: 7 watts nominal.
  • Thermocouple (TC) Ranges
    • Type E: -100°C to +1000°C (-148°F to +1832°F).
    • Type J: -18°C to +760°C (0°F to +1400°F).
    • Type K: -18°C to +1370°C (0°F to +2498°F).
    • Type T: -160°C to +400°C (-256°F to +752°F).
  • RTD Types & Ranges (alpha=0.00385, 100Ω Pt)
    • Standard range: -200°C to +850°C (-328°F to +1562°F).
    • With external barriers: -50°C to +850°C (-122°F to +1562°F).
  • RTD Types & Ranges (alpha=0.00392, 100Ω Pt)
    • Standard range: -200°C to +700°C (-328°F to +1292°F).
    • With external barriers: -50°C to +260°C (-122°F to +1292°F).
  • Nickel & Copper RTD Ranges
    • 120Ω Nickel RTD: -80°C to +260°C (-112°F to +500°F).
    • With external barriers: -50°C to +260°C (-122°F to +500°F).
    • 10Ω Copper RTD: -100°C to +260°C (-148°F to +500°F).
    • With external barriers: -50°C to +260°C (-122°F to +500°F).
  • Outputs & Indicators
    • OK LED: monitor operates correctly.
    • TX/RX LED: monitor communicates with other rack modules.
    • Bypass LED: monitor is in bypass mode.
    • Recorder output: +4 to +20 mA per channel.
    • Short circuits on recorder outputs do not affect monitor operation.
    • RTD current source: 925 ±15 µA at 25°C.
  • Environmental Limits
    • Operating temp with internal/external termination: -30°C to +65°C.
    • Operating temp with internal barrier I/O: 0°C to +65°C.
    • Storage temperature: -40°C to +85°C.
  • Physical Dimensions & Weight
    • Main board: 241.3 x 24.4 x 241.8 mm, 0.91 kg.
    • I/O module (non-barrier): 241.3 x 24.4 x 99.1 mm, 0.45 kg.
    • I/O module (internal barrier): 241.3 x 24.4 x 163.1 mm, 0.46 kg.
    • Requires 1 full-height front slot for monitor.
    • Requires 1 full-height rear slot for I/O module.
  • Agency Approval
    • Option 01: CSA/NRTL/C (Class 1, Div 2).
    • Suitable for hazardous locations with non-incendive requirements.

Installation Guide

  • Install the monitor module in any full-height front slot.
  • Install the matching I/O module in the rear slot behind it.
  • Use 3500/60-01-01 with 3500 series racks only.
  • Connect RTD or TC wires to the I/O module terminals.
  • Set sensor type and range via 3500 configuration software.
  • Observe temperature limits for internal barrier I/O modules (0°C to +65°C).

Package Contents (No certificates, no warranty, no shipping info)

  • 1 x 3500/60-01-01 monitor module (main board)
  • 1 x RTD/TC non-isolated I/O module type 01 (internal terminations)
  • No sensors or cables included

Common FAQs – Practical Answers

  • Can the 3500/60-01-01 mix RTD and TC on different channels?Yes. You can assign each channel independently as RTD or TC.
  • What happens if I short the recorder output wires?No damage occurs. The monitor continues normal operation.
  • Does this module work with 3-wire and 4-wire RTDs?Yes. It supports both 3-wire and 4-wire configurations.
  • What is the minimum operating temperature for this version?With internal terminations, it works from -30°C to +65°C.
  • Is the 3500/60-01-01 approved for Class 1 Div 2 areas?Yes. Agency approval option 01 provides CSA/NRTL/C certification for Class 1, Div 2.

About Ubest

Ubest Automation is a leading global provider of automation products, with deep partnerships with major automation manufacturers to provide customers with customized business solutions, cost-effective products, and comprehensive services.

 

Contact Us

Phone:+86 180 3000 5825

Address:Room 7A, No. 59 Hubin North Road, Siming District Xiamen City China

Email: sales@ubestplc.com

Contact: Klaus

 

Scan the QR code

© 2026, Ubest Automation Limited  All Rights Reserved. sitemap