Introduction:

Allen-Bradley 1746-NI16V SLC 500 Analog Input Module. 16 voltage input channels at 16-bit resolution. Programmable filter frequencies from 6-250 Hz.

ubest aotomation    Customer Reviews

UBEST Automation – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.

Product Attributes:

Manufacturer: Allen‑Bradley
Series: SLC 500
Part Number: 1746-NI16V
Type: Analog Input Module
Condition: In Stock
Origin: U.S.A
Weight: 0.4
Shipping Port: Xiamen
Warranty: One year

Notice: For real-time prices and inventory, please click the button below to contact us.

Description
Inquiry

Product Overview

The Allen-Bradley 1746-NI16V is an analog input module for the SLC 500 system. This module features 16 voltage input channels for various signal ranges. It accepts ±10V DC, 1-5V DC, 0-5V DC, and 0-10V DC signals. The Allen-Bradley 1746-NI16V uses Sigma-Delta conversion with 16-bit resolution. Users trust this module for precise analog measurement in industrial applications.


Technical Specifications

The 1746-NI16V delivers accurate voltage measurement with flexible filtering. Below are the complete technical details.

General Specifications

  • Manufacturer: Rockwell Automation for industrial control reliability.

  • Brand: Allen-Bradley premium automation products.

  • Part Number: 1746-NI16V for precise identification.

  • Series: SLC 500 programmable controller family.

  • Module Type: Analog Input Module.

  • Number of Inputs: Sixteen (16) voltage input channels.

  • Chassis Location: Any I/O module slot except slot 0.

  • Slot Usage: Occupies only one slot in the chassis.

Electrical Signal Types

  • ±10V DC: Bipolar voltage range.

  • 1 to 5V DC: Unipolar with live zero.

  • 0 to 5V DC: Standard unipolar range.

  • 0 to 10V DC: Extended unipolar range.

  • Voltage Category: -10 to +10 Volts DC.

Conversion and Resolution

  • Conversion Type: Sigma - Delta for high accuracy.

  • Resolution: 16 bits for precise measurement.

  • Input Resolution: 312 µV per count.

  • Common Mode Voltage Range: ±10.25 Volts relative to analog common terminal.

  • Input Impedance: 20 Ω for minimal signal loading.

Input Filtering

  • Filter Type: Low-pass digital filter with programmable frequencies.

  • Input Filter Frequencies: 6 Hz, 10 Hz, 20 Hz, 40 Hz, 60 Hz, 80 Hz, 100 Hz, 250 Hz.

  • Bandwidth: 6-250 Hertz depending on filter selection.

  • Step Response: 9-630 milliseconds based on filter setting.

Backplane Current and Power

  • Backplane Current (5 Volts): 125 milliamps.

  • Backplane Current (24 Volts DC): 75 milliamps.

  • Backplane Power Consumption: 2.425 Watts maximum.

  • Power at 5V DC: 0.625 Watts.

  • Power at 24V DC: 1.8 Watts.

Isolation and Approvals

  • Isolation: 500V AC for 1 second between field and logic.

  • UL Listed: Yes for safety compliance.

  • C-UL Approved: Yes for Canadian standards.

  • CE Compliant: For all applicable directives.

  • Hazardous Environment: Approved for Class I Division 2 use.

LED Indicators

  • Number of LEDs: 5 green status indicators.

  • Channel Group Indicators: One LED for each group of 4 channels.

  • Module Status: One dedicated LED for module health.

Temperature and Environmental

  • Operating Temperature: -25 to 60°C (-13 to 140°F).

  • Non-Operating Temperature: -40 to 85°C (-40 to 185°F).

  • Relative Humidity: 5% to 95% without condensation.

  • Operating Vibration: Standard SLC 500 specifications.

  • Operating Shock: Standard SLC 500 specifications.

Drift Specifications

  • Gain Drift: 15 ppm per degree Celsius.

  • Input Offset Drift: 90 mV per degree Celsius.

  • Thermal Stability: Maintains accuracy across temperature range.

Wiring and Termination

  • Recommended Cable: Belden #8761 or equivalent.

  • Terminal Block: Replaceable terminal with part number 1746-RT25G.

  • AIFM Connector: 25-pin D-shell.

  • Pre-Wired Cables: Available in 0.5, 1, 2.5, and 5.0 meter lengths.

  • Compatible Terminal Blocks: 1492-AIFM8-3 and 1492-AIFM16-F-3.

  • Pre-Wired Advantage: Eliminates manual wiring errors with color coding.

Application Suitability

  • Primary Application: Combination 120V AC I/O systems.

  • Installation: Local chassis or expansion chassis (not slot 0).

  • Compatibility: SLC 500 processor via parallel rear-facing interface.


Installation Guide

Follow these steps to install the Allen-Bradley 1746-NI16V correctly.

  1. Power Down the Chassis: Disconnect power before removing or inserting modules.

  2. Locate an Available Slot: Find any empty slot except slot 0 (reserved for CPU).

  3. Align the Module: Position the 1746-NI16V with the slot guides.

  4. Insert the Module: Slide it into the slot until firmly seated.

  5. Secure the Module: Tighten the mounting screws on the top and bottom.

  6. Wire Input Signals: Connect voltage sources to the input terminals.

  7. Use Recommended Cable: Belden #8761 or equivalent shielded cable.

  8. Terminate Wiring: Use replaceable terminal block 1746-RT25G or pre-wired cables.

  9. Select Filter Frequency: Program one of 8 filter settings from 6 to 250 Hz.

  10. Apply Power: Turn on the chassis power to the system.

  11. Monitor Status LEDs: Check the 5 green indicators for proper operation.

  12. Configure Input Ranges: Set each channel for the appropriate voltage range.

  13. Verify Readings: Check analog values in the SLC 500 processor.

  14. Test Step Response: Measure response time based on selected filter.

Installation Notes

  • Do not install this module in slot 0 of the main chassis.

  • Removing or inserting a module with power can cause arcing.

  • The module occupies only one slot in the chassis.

  • Pre-wired cables with 1492 terminal blocks eliminate manual wiring errors.

  • This module is approved for Class I Division 2 hazardous environments.


Packaging List

This unit ships as a new and original product.

  • Allen-Bradley 1746-NI16V SLC 500 Analog Input Module

  • Product data sheet with filter frequency guide

  • Installation instructions

  • Anti-static factory packaging box


Frequently Asked Questions (FAQ)

1. What voltage input ranges does the 1746-NI16V accept?
The Allen-Bradley 1746-NI16V accepts ±10V DC, 1-5V DC, 0-5V DC, and 0-10V DC. Each of the 16 channels can be configured independently.

2. What filter frequencies are available on this analog input module?
The 1746-NI16V offers 8 programmable filter frequencies: 6, 10, 20, 40, 60, 80, 100, and 250 Hz. Step response varies from 9 to 630 milliseconds accordingly.

3. What is the backplane current consumption for the 1746-NI16V?
The Allen-Bradley 1746-NI16V consumes 125 mA at 5V DC and 75 mA at 24V DC. Total backplane power consumption is 2.425 Watts maximum.

4. Can I install this module in slot 0 of the SLC 500 chassis?
No, the 1746-NI16V can be installed in any I/O module slot except slot 0. Slot 0 is reserved for the SLC 500 controller.

5. What are the temperature and humidity ratings for this module?
The Allen-Bradley 1746-NI16V operates from -25 to 60°C with 5-95% non-condensing humidity. Storage temperature ranges from -40 to 85°C.

About Ubest

Ubest Automation is a leading global provider of automation products, with deep partnerships with major automation manufacturers to provide customers with customized business solutions, cost-effective products, and comprehensive services.

 

Contact Us

Phone:+86 180 3000 5825

Address:Room 7A, No. 59 Hubin North Road, Siming District Xiamen City China

Email: [email protected]

Contact: Klaus

 

Industry Links

© 2026, Ubest Automation Limited  All Rights Reserved. sitemap