25A-B017N104 | Allen-Bradley 4 kW 200…240V AC Drive

Introduction:
The Allen-Bradley 25A-B017N104 is a PowerFlex 523 AC drive rated 4 kW (5 HP) at 200…240V AC three-phase, delivering 17.5 A with IP20 open-type enclosure.
Customer Reviews
UBEST Automation – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
Product Attributes:
Notice: For real-time prices and inventory, please click the button below to contact us.
The Allen-Bradley 25A-B017N104 is a AC adjustable-frequency drive — PowerFlex 523 for industrial control and automation applications.
What the Allen-Bradley 25A-B017N104 Delivers in Harsh Conditions
The Allen-Bradley 25A-B017N104 is a PowerFlex 523 AC adjustable-frequency drive rated 4 kW (5 HP) for both normal duty and heavy duty at 200…240V AC, three-phase input, with a continuous output current of 17.5 A. Built for demanding environments, this Frame B drive combines a standard keypad interface with integral brake IGBT and RS-485 DSI communication, making it a dependable choice for mission-critical motor control in oil and gas operations.

How Does This unit Handle Voltage and Power Supply Challenges?
Field engineers often face unstable supply conditions and need a drive that tolerates real-world voltage swings. This model addresses that pain point directly:
- Input voltage: 200…240V AC, three-phase, with a tolerance of -15 % / +10 %.
- Input frequency: 47…63 Hz, accommodating varying generator or grid frequencies.
- Power supply: Three-phase input provides the full rating; single-phase input on this three-phase drive delivers 35 % of the rating.
- Displacement power factor: 0.98 across the entire speed range, reducing reactive power demand.
- Power ride-through: 100 ms, helping the drive ride through short supply interruptions.
- Logic control ride-through: 0.5 s minimum, 2 s typical, maintaining control power during dips.
These electrical specifications mean the drive can be applied where supply quality is less than ideal, a common scenario in remote oil and gas sites. This unit is engineered for harsh oil & gas environments, with a conformal coating that complies with IEC 60721-3-3 level 3C2 (chemical and gases only).
What Operating Temperature Range Suits This Drive?
Thermal management is another critical pain point. This unit offers flexible temperature ratings depending on mounting and enclosure:
- Operating temperature (vertical, IP20/Open Type): -20…+50 °C without derating, up to +60 °C derated, and up to +70 °C with the optional 25-FANx-70C control module fan kit.
- Storage temperature: -40…+85 °C (-40…+185 °F).
- Relative humidity: 0…95 % non-condensing.
- Altitude: 1000 m (3300 ft) maximum without derating; up to 4000 m (13 200 ft) with derating.
- Cooling: Fan cooled; the optional fan kit raises the maximum surrounding air temperature to 70 °C.
For installations in hot climates or enclosed panels, the fan kit option provides an extra margin. The drive is also tested for shock (15 g operating) and vibration (2 g operating) per IEC 60068-2-27 and IEC 60068-2-6:1995, making it rugged enough for demanding environments.
How Does This unit Integrate with Control Systems?
Integration is simplified with a built-in RS-485 DSI port that supports Modbus RTU. The drive provides:
- Digital inputs: 1 dedicated Stop input + 4 programmable; 6 mA input current; SRC mode 18…24V DC = ON / 0…6V DC = OFF; SNK mode 0…6V DC = ON / 18…24V DC = OFF.
- Analog input: 1 isolated, 0…10V DC or 4…20 mA; 10-bit resolution.
- Relay output: 1 programmable Form C; 3.0 A resistive / 0.5 A inductive at 30V DC, 125V AC and 240V AC.
- Analog output: 1 non-isolated, 0…10V or 4…20 mA; 10-bit resolution.
- Communication: RS-485 DSI on RJ45 terminal C1; Modbus RTU with function codes 03, 06 and 16; data rate 1200…38400 bit/s.
For EtherNet/IP, PROFIBUS DP-V1 or DeviceNet, optional communication cards are available (25-COMM-E2P, 25-COMM-P, 25-COMM-D). When wiring into such networks, an external gateway or connection module may be required; confirm cables and gateways with the supplier.
What Protection Features Support Reliable Operation?
Downtime is costly, so This unit includes multiple protection functions:
- Overcurrent: 200 % hardware limit, 300 % instantaneous fault.
- Electronic motor overload: Class 10 protection per NEC article 430, UL 508C File 29572.
- Ground fault trip: Phase-to-ground on the drive output.
- Short-circuit trip: Phase-to-phase on the drive output.
- DC bus overvoltage trip: 405 V DC bus (equivalent to 290 V AC incoming line).
- DC bus undervoltage trip: 190 V DC bus (equivalent to 150 V AC incoming line).
These features help prevent damage and reduce unplanned stoppages. The drive also carries c-UL-us Listing to UL 508C and CSA C22.2 No. 274, and is CE declared to Low Voltage, EMC, Machinery and RoHS directives.
Why Choose This unit for Oil & Gas Applications?
In oil and gas, drives must endure temperature extremes, vibration and corrosive atmospheres. This unit is field-proven in such conditions, with a conformal coating and a wide operating temperature range. Its 4 kW rating at 17.5 A suits medium-duty pumps, fans and conveyors. The drive's efficiency of 97.5 % (typical) helps reduce energy losses, while the displacement power factor of 0.98 minimizes reactive current.
For reliable sourcing of mission-critical spares, PetroPartsOnline offers application-specific selection guidance. Contact PetroPartsOnline for parts suited to your application's requirements.
Frequently Asked Questions
What is the input voltage range of the Allen-Bradley unit?
The Allen-Bradley unit accepts 200…240V AC, three-phase input with a tolerance of -15 % / +10 % and an input frequency range of 47…63 Hz.
Can This unit operate at temperatures above 50 °C?
Yes, the Allen-Bradley unit can operate up to +60 °C with derating, or up to +70 °C when the optional 25-FANx-70C control module fan kit is installed.
Does This unit include an EMC filter?
No, the Allen-Bradley unit has no integral EMC filter; external filters are required to meet EN 61800-3 Category C1/C2/C3 compliance.
What communication protocols does This unit support?
The Allen-Bradley unit has a built-in RS-485 DSI port supporting Modbus RTU; additional protocols like EtherNet/IP require optional communication cards.
Is This unit suitable for single-phase input?
The Allen-Bradley unit is a three-phase drive; applying single-phase input provides 35 % of the rated output.
{"@context": "https://schema.org", "@graph": [{"@type": "Product", "name": "25A-B017N104 | Allen-Bradley 4 kW 200…240V AC Drive", "mpn": "25A-B017N104", "sku": "25A-B017N104", "brand": {"@type": "Brand", "name": "Allen-Bradley"}, "description": "The Allen-Bradley 25A-B017N104 is a AC adjustable-frequency drive — PowerFlex 523 for industrial control and automation applications. What the Allen-Bradley 25A-B017N104 Delivers in Harsh Conditions The Allen-Bradley 25A-B017N104 is a PowerFlex 523 AC adjustable-frequency drive rated 4 kW (5 HP) for both normal duty and heavy duty at 200…240V AC, three-phase input, with a continuous output current of 17.5 A. Built for demanding environments, this Frame B drive combines a standard keypad interfac", "image": ["https://www.petropartsonline.com/wp-content/uploads/2026/11/1793852078-25A-B017N104_1__fp34702284.jpg"], "category": "Drives & Motion Control"}, {"@type": "FAQPage", "mainEntity": [{"@type": "Question", "name": "How Does This unit Handle Voltage and Power Supply Challenges?", "acceptedAnswer": {"@type": "Answer", "text": "Field engineers often face unstable supply conditions and need a drive that tolerates real-world voltage swings. This model addresses that pain point directly: These electrical specifications mean the drive can be applied where supply quality is less than ideal, a common scenario in remote oil and gas sites. This unit is engineered for harsh oil & gas environments, with a conformal coating that complies with IEC 60721-3-3 level 3C2 (chemical and gases only)."}}, {"@type": "Question", "name": "What Operating Temperature Range Suits This Drive?", "acceptedAnswer": {"@type": "Answer", "text": "Thermal management is another critical pain point. This unit offers flexible temperature ratings depending on mounting and enclosure: For installations in hot climates or enclosed panels, the fan kit option provides an extra margin. The drive is also tested for shock (15 g operating) and vibration (2 g operating) per IEC 60068-2-27 and IEC 60068-2-6:1995, making it rugged enough for demanding environments."}}, {"@type": "Question", "name": "How Does This unit Integrate with Control Systems?", "acceptedAnswer": {"@type": "Answer", "text": "Integration is simplified with a built-in RS-485 DSI port that supports Modbus RTU. The drive provides: For EtherNet/IP, PROFIBUS DP-V1 or DeviceNet, optional communication cards are available (25-COMM-E2P, 25-COMM-P, 25-COMM-D). When wiring into such networks, an external gateway or connection module may be required; confirm cables and gateways with the supplier."}}, {"@type": "Question", "name": "What Protection Features Support Reliable Operation?", "acceptedAnswer": {"@type": "Answer", "text": "Downtime is costly, so This unit includes multiple protection functions: These features help prevent damage and reduce unplanned stoppages. The drive also carries c-UL-us Listing to UL 508C and CSA C22.2 No. 274, and is CE declared to Low Voltage, EMC, Machinery and RoHS directives."}}, {"@type": "Question", "name": "Why Choose This unit for Oil & Gas Applications?", "acceptedAnswer": {"@type": "Answer", "text": "In oil and gas, drives must endure temperature extremes, vibration and corrosive atmospheres. This unit is field-proven in such conditions, with a conformal coating and a wide operating temperature range. Its 4 kW rating at 17.5 A suits medium-duty pumps, fans and conveyors. The drive's efficiency of 97.5 % (typical) helps reduce energy losses, while the displacement power factor of 0.98 minimizes reactive current. For reliable sourcing of mission-critical spares, PetroPartsOnline offers application-specific selection guidance. Contact PetroPartsOnline for parts suited to your application's requirements."}}, {"@type": "Question", "name": "What is the input voltage range of the Allen-Bradley unit?", "acceptedAnswer": {"@type": "Answer", "text": "The Allen-Bradley unit accepts 200…240V AC, three-phase input with a tolerance of -15 % / +10 % and an input frequency range of 47…63 Hz."}}, {"@type": "Question", "name": "Can This unit operate at temperatures above 50 °C?", "acceptedAnswer": {"@type": "Answer", "text": "Yes, the Allen-Bradley unit can operate up to +60 °C with derating, or up to +70 °C when the optional 25-FANx-70C control module fan kit is installed."}}, {"@type": "Question", "name": "Does This unit include an EMC filter?", "acceptedAnswer": {"@type": "Answer", "text": "No, the Allen-Bradley unit has no integral EMC filter; external filters are required to meet EN 61800-3 Category C1/C2/C3 compliance."}}, {"@type": "Question", "name": "What communication protocols does This unit support?", "acceptedAnswer": {"@type": "Answer", "text": "The Allen-Bradley unit has a built-in RS-485 DSI port supporting Modbus RTU; additional protocols like EtherNet/IP require optional communication cards."}}, {"@type": "Question", "name": "Is This unit suitable for single-phase input?", "acceptedAnswer": {"@type": "Answer", "text": "The Allen-Bradley unit is a three-phase drive; applying single-phase input provides 35 % of the rated output."}}]}]}