Allen-Bradley 1746-P3 SLC 500 Power Supply 24VDC Input


Introduction:
This Allen-Bradley 1746-P3 is a SLC 500 power supply with 19.2-28.8 VDC input. Provides 3.6 A at 5 VDC and 0.87 A at 24 VDC.
Customer Reviews
UBEST Automation – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
Product Attributes:
Notice: For real-time prices and inventory, please click the button below to contact us.
Product Overview
The Allen-Bradley 1746-P3 is a power supply module for the SLC 500 controller platform. This unit provides power to the 1746 backplane for attached modules. The power supply mounts at the left-most area of the rack. Notably, it does not occupy a chassis slot. Input voltage range spans 19.2 to 28.8 VDC with nominal 24 VDC. Internal current capacity reaches 3.6 Amperes at 5 VDC. Additionally, it delivers 0.87 Amperes at 24 VDC. The 1746-P3 converts input power to voltage levels usable by all SLC 500 modules. Typical line power requirement measures 90 VA. Isolation voltage reaches 600 V AC RMS for 1 second (version B or later). This power supply includes pre-installed fuse protection. For modular control systems, the Allen-Bradley 1746-P3 serves as the essential power source.
Technical Specifications
General Specifications
| Parameter | Value |
|---|---|
| Manufacturer | Rockwell Automation |
| Brand | Allen-Bradley |
| Part Number | 1746-P3 |
| Series | SLC 500 |
| Module Type | Power Supply |
| Location | 1746 Chassis, Left Side |
| UPC | 10662073521430 |
| Weight | 1.1 kg (2.5 pounds) |
| Dimensions | 139.7 x 79.2 x 144.8 mm (5.5 x 2.9 x 5.7 inches) |
Input Specifications
| Parameter | Value |
|---|---|
| Input Voltage Range | 19.2-28.8 VDC |
| Nominal Input Voltage | 24 VDC |
| Input Power | 61 Watts |
| Typical Line Power Requirement | 90 VA |
| Inrush Current | 20 A |
| Frequency | DC |
Output Specifications
| Parameter | Value |
|---|---|
| Current Capacity (5 VDC) | 3.6 Amperes |
| Current Capacity (24 VDC) | 0.87 Amperes |
| Backplane Current (5 Volts) | 3.6 Amps |
| Backplane Current (24 Volts) | 0.87 Amps |
Protection & Isolation Specifications
| Parameter | Value |
|---|---|
| Isolation Voltage | 600 V AC RMS for 1 s (version B or later) |
| Fuse Protection | 1746-F3 or equivalent |
| Hold Up Time (full load) | 5 ms |
| Hold Up Time (no load) | 1000 ms |
| Current Capacity Deration | 5% above 55°C (131°F) |
Environmental Specifications
| Parameter | Value |
|---|---|
| Operating Temperature | 0 to 60°C (32 to 140°F) |
| Altitude | Up to 2000 meters without derating |
| Pollution Degree | 2 |
| Category | II |
Location & Mounting
The 1746-P3 mounts at the left-most area of the SLC 500 rack. Unlike other modules, this power supply does not occupy a chassis slot. Installation requires only a 1/8 inch flat head screwdriver and a 1/4 inch Phillips head screwdriver. The module attaches directly to the backplane on the left side. For system expansion, this design preserves all chassis slots for I/O modules. Consequently, the Allen-Bradley 1746-P3 maximizes usable slot count.
Input Voltage Range
Input voltage range spans 19.2 to 28.8 VDC for flexible power sourcing. Nominal input voltage is 24 VDC standard. Typical line power requirement measures 90 VA for system sizing. Input power consumption reaches 61 Watts under full load. Inrush current peaks at 20 Amperes during startup. For reliable operation, use a suitably rated external 24 VDC supply. The 1746-P3 accepts a wide range of DC input sources.
Output Current Capacity
Current capacity reaches 3.6 Amperes at 5 VDC for logic circuits. At 24 VDC, capacity reaches 0.87 Amperes for relay and output modules. Total backplane current available sums across all installed modules. For system design, calculate total load of all SLC 500 modules. Deration of 5% applies above 55°C (131°F) ambient temperature. Therefore, the Allen-Bradley 1746-P3 supports typical small to medium SLC 500 configurations.
Hold Up Time
Hold up time measures 5 milliseconds at full rated load. At no load, hold up time extends to 1000 milliseconds (1 second). This time represents how long the power supply maintains output after input drops below minimum range. The CPU remains operational during this hold up period. For ride-through capability, the 1746-P3 provides adequate time for brief power disturbances.
Fuse Protection
A pre-installed fuse protects the 1746-P3 from overcurrent conditions. Recommended replacement fuse is Allen-Bradley 1746-F3 or equivalent. Compatible equivalents include BUSSMAN AGC 5 or Nagasawa ULCS-61ML-5 fuses. Fuse sizes declared are for end-devices only. Reduction may be possible depending on circuit wiring size. For maintenance, keep spare fuses available. The Allen-Bradley 1746-P3 allows field fuse replacement when needed.
Isolation & Dielectric Withstand
Isolation voltage reaches 600 V AC RMS for 1 second on version B or later. No isolation exists between the backplane and input terminals. However, dielectric withstand between chassis ground terminal and input terminals reaches 600 V AC RMS for 1 second. This rating ensures safety for grounded installations. For electrical safety, the 1746-P3 meets standard industrial requirements.
Hazardous Location Certifications
The 1746-P3 carries Class 1, Division 2, Groups A, B, C, D hazardous location certifications. Underwriter’s Laboratories (UL) lists this module as Industrial Control Equipment for hazardous locations. C-UL provides similar listing for Canadian installations. For petrochemical and other hazardous area applications, this certification proves essential. Consequently, the Allen-Bradley 1746-P3 suits installations in Division 2 environments.
ESD Protection Guidelines
Keep the module in static-shield packaging when not in use. Avoid touching the connector pins and backplane connector. Additionally, avoid touching circuit components on the module. Static discharge can damage sensitive electronic components. For long-term reliability, follow ESD protection practices. The 1746-P3 requires careful handling during installation and maintenance.
Installation Guidelines
Follow these steps for proper installation of the 1746-P3.
Power down the entire SLC 500 system before installation.
Open the chassis left side for power supply mounting access.
Align the 1746-P3 with the left-side backplane connector.
Press the module firmly into place until fully seated.
Secure the power supply using the mounting screws provided.
Connect 24 VDC input power to the terminal block (19.2-28.8 VDC).
Verify proper grounding through the chassis ground terminal.
Power up the system and check backplane voltage levels.
Note: The 1746-P3 mounts at the left-most area of the rack and does not occupy a chassis slot. Use only recommended fuses (1746-F3 or equivalent) for replacement. Current capacity derates 5% above 55°C ambient temperature. For Class 1 Division 2 hazardous locations, observe all installation codes.
Packaging List
One Allen-Bradley 1746-P3 SLC 500 Power Supply
One pre-installed fuse (1746-F3 or equivalent)
One product installation manual
One anti-static protective bag
Common FAQs
1. What is the input voltage range of the 1746-P3?
Input voltage spans 19.2 to 28.8 VDC with nominal 24 VDC. Typical line power requirement measures 90 VA for system sizing. Input power consumption reaches 61 Watts under full load. Inrush current peaks at 20 Amperes during startup. For reliable operation, the Allen-Bradley 1746-P3 accepts a wide range of DC input sources.
2. What output current does the 1746-P3 provide?
Current capacity reaches 3.6 Amperes at 5 VDC for logic circuits. At 24 VDC, capacity reaches 0.87 Amperes for relay and output modules. Deration of 5% applies above 55°C (131°F) ambient temperature. For system design, calculate total load of all SLC 500 modules. The Allen-Bradley 1746-P3 supports typical small to medium configurations.
3. Where does the 1746-P3 mount in the SLC 500 chassis?
The power supply mounts at the left-most area of the rack. Unlike other modules, this power supply does not occupy a chassis slot. Installation requires only a 1/8 inch flat head and 1/4 inch Phillips head screwdriver. For system expansion, this design preserves all chassis slots for I/O modules. Consequently, the Allen-Bradley 1746-P3 maximizes usable slot count.
4. What replacement fuses work with the 1746-P3?
Recommended replacement fuse is Allen-Bradley 1746-F3 or equivalent. Compatible equivalents include BUSSMAN AGC 5 or Nagasawa ULCS-61ML-5 fuses. Fuse sizes declared are for end-devices only. Reduction may be possible depending on circuit wiring size. The Allen-Bradley 1746-P3 allows field fuse replacement when needed.
5. What hazardous location certifications does the 1746-P3 hold?
This power supply carries Class 1, Division 2, Groups A, B, C, D hazardous location certifications. UL lists this module as Industrial Control Equipment for hazardous locations. C-UL provides similar listing for Canadian installations. For petrochemical applications, the Allen-Bradley 1746-P3 suits Division 2 hazardous area installations.
Why Choose This Power Supply?
The Allen-Bradley 1746-P3 delivers reliable DC power for SLC 500 systems. Input range of 19.2-28.8 VDC accepts standard 24 VDC industrial supplies. Output of 3.6 A at 5 V and 0.87 A at 24 V supports typical chassis configurations. Left-side mounting preserves all I/O slots for modules. Class 1 Division 2 hazardous location certification expands application flexibility. Fuse protection and 600 V isolation ensure safe operation. For SLC 500 systems requiring DC input power, choose the 1746-P3.