TSXDEY16D2 | Schneider Electric 16-Point DC Input Module



Introduction:
The TSXDEY16D2 is a field-proven Modicon Premium 16-point DC input module with 24 VDC sink inputs, 1500 VAC isolation, and 4 ms response—built for demanding oil & gas control cabinets.
Customer Reviews
UBEST Automation – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
Product Attributes:
Notice: For real-time prices and inventory, please click the button below to contact us.
Product Overview: TSXDEY16D2 Modicon Premium Input Module
When specifying discrete input modules for oil & gas control cabinets, engineers need predictable electrical behavior and rugged construction. The TSXDEY16D2 from Schneider Electric is a 16-point DC input module in the Modicon Premium series, designed for 24 V DC sink (negative logic) field signals. With channel-to-bus isolation of 1500 V AC and a typical 4 ms response time, it is built for demanding environments where signal integrity and uptime are mission-critical.
This buyer’s guide covers the key specifications, compatibility, and lifecycle considerations to help you evaluate whether the TSXDEY16D2 fits your application—or whether a replacement path is needed.

Key Features & Technical Specifications
- Channels: 16 points arranged in 2 groups of 8, allowing flexible wiring for discrete sensors.
- Signal type: DC input, sink (negative logic), compatible with common 24 V DC field devices.
- Voltage range: 24 V DC nominal field input; backplane supply 5 V DC.
- Input current: 7 mA per channel at state 1, minimizing load on field power supplies.
- Isolation: 1500 V AC dielectric channel-to-bus; isolation resistance >10 MΩ at 500 V.
- Response time: 4 ms typical, suitable for most discrete monitoring and interlock loops.
- Power consumption: 0.97 W, with bus current 80 mA at 5 V DC.
- Slots required: 1 slot in a Modicon Premium rack.
- Protection rating: IP20 for cabinet-mounted installation.
- Dimensions: 140 × 35 × 80 mm; weight 0.15 kg.
Note: Operating temperature, storage temperature, and relative humidity are not available in the provided data. Refer to the official Schneider Electric datasheet for environmental limits.
Applications & Use Cases
The TSXDEY16D2 is well-suited to oil & gas applications where 24 V DC discrete signals must be reliably captured. Typical uses include monitoring limit switches on valve actuators, reading pressure and flow switch status, and interfacing with pushbuttons and relay contacts in control panels. In upstream wellhead panels, the 1500 V AC isolation helps protect the PLC backplane from transients induced by nearby motors or solenoids. The 4 ms response time is adequate for most alarm and interlock functions, though high-speed counting should be verified against loop requirements. For midstream compressor stations, the module’s 16-point density in a single slot helps conserve rack space. Because the product is discontinued, it is often specified for existing Modicon Premium systems requiring like-for-like replacement or spares.

Compatibility & Integration
The TSXDEY16D2 is designed for the Modicon Premium PLC platform, occupying one slot in a compatible rack. It communicates via the backplane, drawing 80 mA at 5 V DC. Field wiring connects to the module’s front connector (not included) for 24 V DC sink inputs. When integrating with fieldbus networks such as PROFINET, EtherNet/IP, or DeviceNet, note that the module itself does not provide a fieldbus interface; an external gateway or communication module may be required. Confirm cable and gateway compatibility with your supplier before commissioning.
Installation & Setup Guidance
Mount the module in a Modicon Premium rack following the manufacturer’s slot rules. Ensure the rack power supply can deliver the additional 80 mA at 5 V DC and account for 0.97 W power consumption when calculating thermal load. Use shielded twisted-pair cable for field inputs, grounding the shield at the cabinet entry. Because the module uses sink (negative logic) inputs, verify that field devices switch to 0 V DC. Tighten terminal screws to the recommended torque and label each channel to simplify troubleshooting. The IP20 rating requires installation inside a protective enclosure; avoid exposing the module to conductive dust or moisture.
Maintenance & Reliability
In oil & gas environments, regular inspection of field wiring and connectors is recommended to prevent intermittent faults. Check for loose terminals, corrosion, and cable damage during scheduled maintenance outages. The module’s 1500 V AC isolation provides a barrier against common-mode transients, but surge protection on field wiring is still advised in areas with high electrical noise. Because operating temperature specifications are not available, monitor cabinet temperature and ensure adequate ventilation. The TSXDEY16D2 is a field-proven component, but its discontinued status means spare units should be sourced proactively to avoid downtime. PetroPartsOnline can help you secure reliable spares for critical operations.
Lifecycle & Sourcing Considerations
The TSXDEY16D2 is marked as discontinued (last verified 2026-09). For new projects, consider migrating to a current Modicon platform; for existing installations, stock spares to extend service life. PetroPartsOnline specializes in sourcing hard-to-find automation parts, including discontinued Schneider Electric modules. Contact PetroPartsOnline for parts suited to your application’s requirements and to discuss availability.
FAQ
Q: What is the input voltage and current for the TSXDEY16D2?
A: The module accepts 24 V DC field input, with 7 mA per channel in state 1. The backplane supply is 5 V DC, and bus current draw is 80 mA at 5 V DC.
Q: What isolation does the TSXDEY16D2 provide?
A: It offers 1500 V AC dielectric isolation channel-to-bus and isolation resistance greater than 10 MΩ at 500 V, protecting the backplane from field transients.
Q: Is the TSXDEY16D2 still available?
A: The product is discontinued (last verified 2026-09). Contact PetroPartsOnline for current stock or suitable replacement options for your Modicon Premium system.
Q: What is the response time of the TSXDEY16D2?
A: Typical response time is 4 ms, suitable for most discrete monitoring and interlock applications in oil & gas control systems.
Q: Can the TSXDEY16D2 be used with fieldbus networks?
A: The module communicates via the Modicon Premium backplane. For fieldbus integration such as PROFINET or EtherNet/IP, an external gateway or communication module may be required. Confirm compatibility with your supplier.