+86 18030005825
No.95, Xiangxing Road, Xiang'an District, Xiamen

MTL3041 Eaton MTL | Isolated 4/20mA Repeater Power Supply Zone 0

Introduction:

The MTL3041 is an isolated repeater power supply for 2-wire 4/20mA transmitters. It provides 17.5V at 20mA for Zone 0 IIC areas.

ubest aotomation    Customer Reviews

UBEST Automation – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.

Product Attributes:

Manufacturer: MTL (Measurement Technology Ltd.)
Series: MTL3000 Series
Part Number: MTL3041
Type: Isolated Repeater Power Supply / 4/20mA Repeater
Condition: Subject to stock check
Weight: 0.16
Shipping Port: Xiamen
Warranty: One year

Notice: For real-time prices and inventory, please click the button below to contact us.

Description
Inquiry

Eaton MTL3041 Isolated Repeater Power Supply for 4/20mA Transmitters

Product Overview

A high-performance isolated repeater arrives as the MTL3041 from Eaton’s MTL series. This device provides a fully-floating DC supply for hazardous-area 2-wire transmitters. The MTL3041 repeats the 4/20mA current accurately in another floating circuit. Engineers use this module to drive safe-area loads from hazardous-area measurements. Consequently, the MTL3041 suits Zone 0, IIC, T4-T6 hazardous areas when certified. The transformer-coupled circuit chops the 4/20mA current directly for exceptional stability. Furthermore, the 17.5V output at 20mA exceeds normal transmitter loop requirements.

Technical Specifications

ParameterSpecification
ManufacturerEaton (MTL)
ModelMTL3041
Product TypeIsolated Repeater Power Supply
Number of Channels1, fully floating
Location of TransmitterZone 0, IIC, T4-T6 / Div. 1, Group A
Voltage at 20mA (min)17.5V
Open Circuit Voltage (max)28V
Input/Output Signal Range4 to 20mA (0 to 20mA full range)
Safe-area Load Resistance0 to 800Ω
Safe-area Output Resistance>1MΩ
Safe-area Circuit Ripple<10µA peak-to-peak
Transfer Accuracy (20°C)Better than 20µA
Temperature Drift<1µA/°C
Response Time<60ms (to 10% of final value)
Power Consumption (24V, 20mA)100mA typical
Power Dissipation (24V, 20mA)2.0W typical
Power Dissipation (35V, 20mA)2.5W maximum
Replaceable Fuse125mA, 5x20mm glass, semi-time-lag
Safety Description28V, 300Ω, 93mA; Um=250V rms/DC
FM Entity ParametersVoc=28V, Isc=93mA, Ca=0.13µF, La=4.0mH
Weight160g

Loop Power Specifications

The MTL3041 provides robust power for 2-wire transmitter loops. Minimum output voltage reaches 17.5V at 20mA for consistent transmitter operation. Maximum open-circuit voltage equals 28V for adequate headroom. Thus, the MTL3041 powers all normal 4/20mA transmitter loops reliably. The floating output allows field cables to be earthed intentionally or by error. Therefore, grounding does not compromise measurement integrity or safety.

Maximum permitted line resistance depends on transmitter voltage requirements. Calculate using the formula: (17.5V minus transmitter voltage) x 50Ω. For a transmitter requiring 12V, maximum line resistance equals 275Ω. Thus, the MTL3041 accommodates long cable runs in many installations.

Signal Range and Load Drive

The MTL3041 accepts and repeats a wide range of current signals. Signal range covers 4 to 20mA for standard process control applications. Full range capability extends from 0 to 20mA for additional flexibility. Thus, the MTL3041 works with both traditional and extended range transmitters. Safe-area load resistance accepts 0 to 800Ω for flexible integration. Output resistance exceeds 1MΩ for minimal loading on the current loop.

The high output resistance ensures excellent current source behavior. Therefore, the MTL3041 maintains accuracy even with varying load conditions. Safe-area circuits can drive PLC inputs, indicators, and recorders directly.

Transfer Accuracy and Stability

The MTL3041 delivers exceptional accuracy for critical process measurements. Transfer accuracy at 20°C exceeds 20µA for precise signal reproduction. Typical performance is significantly better than this specification. Thus, the MTL3041 preserves measurement integrity across the isolation barrier. Temperature drift stays below 1µA per degree Celsius for stable operation. Therefore, accuracy remains consistent despite ambient temperature changes.

The transformer-coupled circuit eliminates high-stability resistors entirely. Consequently, the MTL3041 achieves extremely high long-term stability. Short-term stability matches this exceptional long-term performance. Thus, recalibration intervals can extend significantly compared to conventional designs.

Signal Quality and Ripple

The MTL3041 maintains exceptionally clean output signals for sensitive applications. Safe-area circuit ripple stays below 10µA peak-to-peak maximum. Thus, the MTL3041 adds minimal noise to process measurement loops. Low ripple preserves signal resolution for high-precision control applications. Therefore, the MTL3041 suits demanding processes requiring clean analog signals.

The floating circuit design eliminates ground loop errors completely. Consequently, measurement accuracy improves in systems with multiple ground points. The MTL3041 breaks unwanted ground paths while passing signal information faithfully.

Response Time

The MTL3041 responds promptly to input signal changes. Settling reaches within 10% of final value in under 60 milliseconds typically. Thus, the MTL3041 suits most process control applications easily. This response time supports typical temperature, pressure, and flow measurements effectively. Faster loops may experience slight delay due to the transformer-coupled design.

For standard 4/20mA process signals, response is more than adequate. Therefore, the MTL3041 introduces acceptable delay to most control loops. Process dynamics typically dominate overall system response time.

Floating Output Benefits

The MTL3041 features a fully-floating output circuit for maximum flexibility. This floating design allows field cables to be earthed without measurement errors. Thus, accidental grounding does not compromise loop integrity or accuracy. The floating output also solves problems with control computers connected independently to earth. Some instrument manufacturers demand such independent earthing for their equipment.

Isolation of the safe-area circuit from the 24V DC supply simplifies wiring. Therefore, the MTL3041 eliminates measurement errors due to voltage drops in shared cables. Shared return paths no longer introduce inaccuracies into the 4/20mA measurement.

Power Requirements

The MTL3041 requires 20 to 35V DC supply voltage for operation. Typical current consumption reaches 100mA at 24V with 20mA signal. Consumption varies from 125mA at 20V to 80mA at 35V with 20mA signal. Thus, the MTL3041 operates efficiently across its supply range. Power dissipation equals 2.0W typical at 24V with 20mA signal. Maximum dissipation reaches 2.5W at 35V under the same signal condition.

The replaceable fuse protects against internal faults. Fuse rating is 125mA, 5x20mm glass, semi-time-lag type. Thus, field replacement is possible if the fuse ever opens. Always use the correct fuse type for the MTL3041.

Safety Description and Entity Parameters

The MTL3041 carries important safety parameters for hazardous area installations. Safety description specifies 28V, 300Ω, 93mA with Um=250V rms/DC. Thus, the MTL3041 limits energy to safe levels for Zone 0 areas. FM entity parameters include Voc=28V, Isc=93mA for North American installations. Associated capacitance (Ca) equals 0.13µF for cable length calculations. Associated inductance (La) equals 4.0mH for cable inductance limits.

These parameters allow connection of approved field devices without recalculation. Therefore, the MTL3041 simplifies hazardous area loop design. Always verify that field device parameters remain within these limits.

Smart Transmitter Note

The MTL3041 works with conventional 4/20mA transmitters only. For applications involving smart transmitters, use the MTL3046B instead. Smart transmitters require different impedance characteristics for digital communication. Thus, the MTL3041 does not support HART or other digital protocols. The MTL3046B provides the necessary filtering and impedance for smart devices.

Verify your transmitter type before selecting the MTL3041. Conventional analog transmitters work perfectly with this model. Therefore, check your device specifications before ordering.

Installation Guide

Follow these steps to install the MTL3041 correctly.

  1. Power Down System: De-energize all circuits before installation begins.

  2. Mount Unit: Secure the MTL3041 to DIN rail in a safe-area enclosure.

  3. Connect Supply: Wire 20-35V DC to the supply terminals (see manual for polarity).

  4. Wire Transmitter: Connect hazardous-area 2-wire transmitter to input terminals.

  5. Wire Safe Load: Connect safe-area receiving instrument to output terminals.

  6. Verify Polarity: Ensure correct polarity for both input and output connections.

  7. Check Fuse: Verify the 125mA fuse is intact before applying power.

  8. Apply Power: Energize the MTL3041 and verify loop operation.

  9. Test Signal: Apply 4-20mA input and confirm output matches accurately.

Important: Never connect loads exceeding 800Ω to the MTL3041 safe-area output. Always maintain proper segregation between hazardous and safe wiring. The device provides isolation, but physical separation remains best practice. Finally, use the MTL3046B for smart transmitter applications.

Key Features and Benefits

  • Fully-Floating Supply: Allows field cables to be earthed without measurement errors, simplifying installation.

  • High Loop Power: Provides 17.5V at 20mA for all normal transmitter loops, ensuring reliable operation.

  • Exceptional Stability: Transformer-coupled circuit eliminates high-stability resistors, achieving long-term accuracy.

  • Low Output Ripple: Stays below 10µA peak-to-peak for clean signals, preserving measurement resolution.

  • High Load Drive: Drives safe-area loads up to 800Ω for flexible integration, accommodating various receivers.

  • Zone 0 IIC Compatible: Suits highest risk hazardous areas including hydrogen, enabling critical applications.

The MTL3041 delivers reliable isolated power and signal repeat for 4/20mA transmitters. Consequently, this repeater suits Zone 0 IIC hazardous areas requiring accurate measurement. Its 17.5V output powers all normal transmitter loops, while the floating design allows cable earthing. The transfer accuracy exceeds 20µA, yet temperature drift stays below 1µA/°C. Environmental compatibility includes Zone 0, IIC, T4-T6 hazardous areas for global installations.

Package Contents

  • One MTL3041 isolated repeater power supply module

  • One 125mA replaceable fuse (installed)

  • One terminal label sheet

  • One installation instruction sheet

Frequently Asked Questions (FAQ)

1. What is the maximum load resistance for the MTL3041 safe-area output?

The MTL3041 drives safe-area loads from 0 to 800Ω maximum. This range accommodates most PLC inputs, indicators, and recorders. Thus, verify your receiving instrument impedance before connection.

2. Can the MTL3041 be used with smart/HART transmitters?

No, the MTL3041 is designed for conventional 4/20mA transmitters only. For smart transmitter applications, use the MTL3046B instead. Thus, check your transmitter type before selecting this model.

3. What hazardous area locations does the MTL3041 support?

The MTL3041 supports Zone 0, IIC, T4-T6 hazardous areas under IEC standards. For North America, Div. 1, Group A hazardous locations are acceptable. Thus, this device suits hydrogen, acetylene, and other IIC gas groups.

4. What is the maximum permitted line resistance for the MTL3041?

Maximum line resistance equals (17.5V minus transmitter voltage) x 50Ω. For a transmitter requiring 12V, the limit is 275Ω. Thus, long cable runs are possible with low-voltage transmitters.

5. Does the MTL3041 require external loop power for the safe-area output?

No, the MTL3041 output is fully powered from the 20-35V DC supply. It does not require external loop power for the safe-area circuit. Thus, wiring remains simple with only the supply voltage connection needed.

About Ubest

Ubest Automation is a leading global provider of automation products, with deep partnerships with major automation manufacturers to provide customers with customized business solutions, cost-effective products, and comprehensive services.

 

Contact Us

Phone:+86 180 3000 5825

Address:Room 7A, No. 59 Hubin North Road, Siming District Xiamen City China

Email: [email protected]

Contact: Klaus

 

Industry Links

© 2026, Ubest Automation Limited  All Rights Reserved. sitemap