Honeywell 900H03-0202 8 Channel Digital Output 240VAC


Introduction:
This page describes the Honeywell 900H03-0202 digital output module. It provides 8 isolated Triac outputs for 120 to 240 VAC loads. Each output has MOV protection and a field-replaceable fuse.
Customer Reviews
UBEST Automation – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
Product Attributes:
Notice: For real-time prices and inventory, please click the button below to contact us.
Honeywell 900H03-0202 Digital Output Module Overview
The Honeywell 900H03-0202 is an 8 channel AC digital output module. It belongs to the 900 Series from Honeywell. This module provides zero switching Triac solid-state outputs. Each output has a MOV for transient over-voltage protection. The 900H03-0202 includes a field-replaceable fuse per channel. A green LED indicator shows when each output is ON.
Technical Specifications of 900H03-0202
The Honeywell 900H03-0202 has 8 outputs per module. Operating voltage ranges from 85 VAC to 240 VAC. Peak voltage handling is 250 VAC. AC frequency acceptance is 47 Hz to 63 Hz. Output type is Triac with zero voltage switching. Galvanic isolation exists between each output and logic.
Maximum load current is 2 Amps per point. Total module load current is 8 Amps maximum for resistive loads. ON voltage drop is less than 2.0 VAC above 0.1 Amp. Below 0.1 Amp, the drop is less than 3.0 VAC. Maximum leakage current is 4 mA at 240 VAC and 60 Hz. At 100 VAC and 60 Hz, leakage is 1.2 mA. At 100 VAC and 50 Hz, leakage is 0.9 mA.
Maximum inrush current is 15 Amps for 10 milliseconds. Minimum load requirement is 50 mA. OFF to ON response time is 3 ms plus 0.5 line cycle maximum. ON to OFF response time is also 3 ms plus 0.5 line cycle. These response times exclude controller scan time and backplane transmission.
Each output on the 900H03-0202 contains a 3.15 Amp time-lag fuse. The replacement fuse is Littelfuse 37413150410. Failsafe state configuration supports two options. Hold Last State keeps the previous output condition. Failsafe State applies a user-specified output value. A green blinking status LED indicates module scanning. A red status LED lights when module diagnostics exist.
A shorting comb (900J02-0001 or 900J10-0001) is available separately. This comb simplifies connections to a common voltage source. It works with barrier type terminal blocks only. The module provides MOV protection on every output. This protects against voltage spikes and transients.
Installation Guidelines for Honeywell 900H03-0202
Mount the 900H03-0202 in a Honeywell 900 Series rack. Select a slot away from low voltage modules. Push the module in until the connectors engage fully. Secure the module with the locking latch at the bottom. Connect AC load wiring to the removable terminal block.
Use the shorting comb for common voltage connections. Install the comb across all barrier terminals for the same phase. Connect the AC supply to the comb input point. Install a fuse or circuit breaker on each output line. Do not exceed 2 Amps per output channel.
Configure failsafe behavior using Honeywell Control Builder software. Set each output to Hold Last State or a specific value. Download the configuration to the controller. Verify the green LED blinks to confirm scanning. Test each output by turning it ON from the controller.
Package Contents of 900H03-0202
Your shipment includes these items:
One Honeywell 900H03-0202 digital output module
One removable terminal block for AC wiring
One locking latch for module retention
One installation instruction sheet
Eight output channel labels for identification
The package does not include the shorting comb. You must purchase comb 900J02-0001 separately. No replacement fuses are provided with this module.
Frequently Asked Questions about 900H03-0202
1. What loads can I switch with the 900H03-0202?
The Honeywell 900H03-0202 switches resistive AC loads only. It works with heaters, lamps, and solenoids. Do not use it for inductive loads like motors or transformers. Inductive loads may damage the Triac outputs.
2. How do I replace a blown fuse on this module?
Each channel on 900H03-0202 has a field-replaceable fuse. Remove power from the module first. Open the fuse holder on the top of the module. Replace the blown fuse with Littelfuse 37413150410 (3.15A time-lag).
3. What is the shorting comb used for on 900H03-0202?
The shorting comb connects all outputs to a common AC source. This saves wiring time for Honeywell 900H03-0202 installations. Order comb model 900J02-0001 or 900J10-0001 separately. The comb works only with barrier type terminal blocks.
4. Can I use 900H03-0202 with 24 VAC control signals?
No, the 900H03-0202 requires 85 to 240 VAC operating voltage. It cannot switch 24 VAC loads reliably. For 24 VAC outputs, use a different Honeywell module. Check the catalog for low voltage AC output options.
5. What does the red LED indicate on this module?
A red LED on Honeywell 900H03-0202 means a diagnostic condition exists. This could be a blown fuse or configuration error. It may also signal an over-temperature or supply problem. Check the controller for specific fault codes.
Compatibility and Application Notes
The Honeywell 900H03-0202 works with Honeywell 900 Series controllers. It suits building automation and industrial heating control. Use it for valve actuation and pilot light switching. Each output includes a green LED for local status indication. The MOV protection handles surges up to 250 VAC peak. This module is not RoHS 2 compliant as a spare part. For new installations, order the updated version. The HS code for customs is 85389000. Dispose of this module according to local WEEE regulations.