Introduction:
The ATV930D90N4Z is a dual-rated 90 kW variable speed drive from Schneider Electric, built for rugged oil and gas duty with integrated safety and Ethernet.
Customer Reviews
UBEST Automation – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
Product Attributes:
Notice: For real-time prices and inventory, please click the button below to contact us.
ATV930D90N4Z: A Field-Proven Drive for Demanding Oil & Gas Operations
The ATV930D90N4Z is a three-phase variable speed drive from Schneider Electric’s Altivar Process ATV930 series. It delivers 90 kW in normal duty and 75 kW in heavy duty, operating from a 380…480 V supply with an integrated EMC filter.
For decades, oil and gas operators relied on fixed-speed motors and mechanical throttling to control pumps and fans. That approach wasted energy and added wear. The shift toward variable speed control changed the equation. This unit continues that evolution, combining robust power electronics with integrated safety and networking.

Key Technical Specifications
The drive is dual-rated, meaning it can serve both normal-duty and heavy-duty applications. Below are the core parameters for this model.
- Supply voltage: 380…480 V three-phase (-15%/+10%), 50/60 Hz.
- Motor power (ND): 90 kW (125 HP), 120% overload for 60 s.
- Motor power (HD): 75 kW (100 HP), 150% overload for 60 s.
- Operating temperature: 0 to +40 °C standard, derating to 50 °C.
- Storage temperature: -40 to +70 °C.
- Protection rating: IP20 (bottom power terminals IP00).
- Dimensions (H×W×D): 748 x 265 x 307 mm.
- Integrated safety: STO function, SIL3 / Cat. PL e.
- Built-in ports: Ethernet dual-port switch and Modbus serial.
- EMC filter: Category C3 integrated.
Failure Mode Analysis: Designing for Reliability
Variable speed drives in oil and gas face heat, vibration, and harsh air. This unit addresses these failure modes with specific design choices.
First, thermal management is critical. The drive requires a minimum air flow of 295 m3/h. It also needs 100 mm clearance above and below for convection. Ignoring these values leads to overheating and premature capacitor failure. Second, the integrated EMC filter reduces electrical noise that can disrupt nearby instrumentation. Third, the built-in braking transistor handles regenerative energy from high-inertia loads. However, an external braking resistor is required, with a minimum resistance of 2.5 Ω. Without proper braking, overvoltage trips can occur.
The environmental class is IEC 60721-3-3 class 3C3 / 3S3 / 3M3, which covers many industrial settings. For offshore or dusty locations, verify the class against your site conditions.

Installation and Setup Guidance
This is a cabinet integration version, so it is designed for mounting inside an enclosure. The IP20 rating protects against finger contact but not dust or water. Therefore, the cabinet must provide the primary environmental protection.
Wiring requires attention to terminal torque. Frame 5 power terminals need 25 N·m. The drive includes 8 digital inputs, 3 analog inputs, 2 analog outputs, and 3 relay outputs. These can handle most control needs. For additional I/O, up to 3 expansion modules can be added.
When integrating into a network, the built-in Ethernet port supports EtherNet/IP and Modbus TCP. The serial port supports Modbus RTU. For other fieldbuses, an option slot accepts modules for PROFINET, PROFIBUS DP, CANopen, DeviceNet, EtherCAT, or POWERLINK. Note that wiring into such networks may require an external gateway or connection module. Confirm cables and gateways with your supplier.
Applications in Oil & Gas
This unit suits mission-critical applications where reliability is essential. Common uses include pump jacks, pipeline pumps, and compressor fans. The dual rating allows one drive to serve both continuous and high-overload duties. For example, a heavy-duty mud pump might use the 75 kW HD rating, while a normal-duty cooling fan uses the 90 kW ND rating. The integrated STO function supports safety circuits up to SIL3, which is valuable for emergency stops. The drive is also built for demanding environments, with an operating temperature range that covers most cabinet installations.
Maintenance and Long-Term Reliability
Regular inspection extends drive life. Check cooling fans and air filters every few months. Verify that the minimum air flow of 295 m3/h is maintained. Inspect power connections for tightness, especially after thermal cycling. The drive stores diagnostic data, which can help predict wear. Because This unit is an active model in Schneider Electric’s catalog, long-term support is expected. Please verify current lifecycle status and availability with PetroPartsOnline before ordering.
FAQ
What is the supply voltage for This unit?
This unit operates on a 380…480 V three-phase supply with -15%/+10% tolerance at 50/60 Hz.
Can This unit be used in a cabinet without additional cooling?
The drive requires a minimum air flow of 295 m3/h and 100 mm clearance above and below. Without adequate cooling, derating or overheating may occur.
What is the operating temperature range of This unit?
The standard operating temperature is 0 to +40 °C. Derating is required from 40 to 50 °C. Storage temperature ranges from -40 to +70 °C.
Does This unit include a braking resistor?
No, the drive includes a built-in dynamic brake transistor but requires an external braking resistor. The minimum resistance is 2.5 Ω.
What safety functions are integrated into This unit?
The drive includes a Safe Torque Off (STO) function certified to SIL3 / Cat. PL e per IEC 61508 and ISO 13849-1.
Contact PetroPartsOnline for parts suited to your application’s requirements.