1746-NIO4I Combination Module | Voltage/Current Inputs


Introduction:
The 1746-NIO4I is an SLC 500 analog combination module from Allen-Bradley. It provides 2 inputs and 2 outputs with 16-bit input resolution.
Customer Reviews
UBEST Automation – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
Product Attributes:
Notice: For real-time prices and inventory, please click the button below to contact us.
Product Overview for the 1746-NIO4I Analog Combination Module
The 1746-NIO4I is an SLC 500 analog combination module from Allen-Bradley. Firstly, this module is manufactured by Rockwell Automation under the Allen-Bradley brand. Specifically, the 1746-NIO4I provides two (2) inputs and two (2) output points in a single slot module. In addition, this combination module features differential voltage or current input points. The outputs are dedicated current channels for precise control. Consequently, the 1746-NIO4I is ideal for applications requiring both analog measurement and control in a compact footprint. Therefore, this module saves valuable panel space in SLC 500 systems.
Channel Configuration and I/O Capabilities
Two Configurable Input Channels
The 1746-NIO4I offers two differential input channels. Firstly, each input accepts either voltage or current signals. In addition, the voltage range is -10 to +10V DC for standard analog sensors. The current range is -20 to +20 mA for process transmitters. Specifically, the voltage input impedance is 760 kOhms for minimal signal loading. The current input impedance is 250 Ohms. Consequently, the 1746-NIO4I connects directly to most analog field devices without external signal conditioners.
Two Current Output Channels
The 1746-NIO4I provides two current output channels for precise control. Firstly, the normal output range is 0 to 20 mA for standard actuators. In addition, a 5% over-range capability extends control beyond 20 mA. Specifically, the load range is 0 to 500 mA for driving various field devices. The output resolution is 2.56348 microAmps per LSB. Consequently, the 1746-NIO4I delivers smooth, precise control for valves and positioners.
Raw Data Scaling
The 1746-NIO4I converts analog signals to raw data values for the PLC. Firstly, current input signals translate to raw data from -16,384 to +16,384. In addition, voltage input signals translate to raw data from -32,768 to +32,767. Specifically, the voltage resolution is 305 microVolts per least significant bit (LSB). The current resolution is 1.22 microAmps per LSB. Consequently, you can scale these raw values to engineering units in your SLC 500 program.
Resolution and Conversion Performance
High Resolution Analog Conversion
The 1746-NIO4I uses Sigma-Delta ADC converter technology. Firstly, the input converter resolution is 16 bits for high precision measurement. In addition, the output converter resolution is 14 bits for smooth control signals. Specifically, repeatability is ±1 LSB for consistent readings. Non-linearity is 0.05% for output accuracy. Consequently, the 1746-NIO4I provides reliable analog data for critical process applications.
Fast Update Time
The 1746-NIO4I delivers rapid analog data updates for responsive control. Firstly, the aggregate update time is 512 microseconds for all channels. In addition, the input step response is 60 milliseconds for signal changes. Specifically, the output step response is 2.5 milliseconds for fast actuation. Consequently, the 1746-NIO4I supports demanding process and motion control applications.
Accuracy and Environmental Stability
Temperature Compensated Accuracy
The 1746-NIO4I maintains accuracy across its operating temperature range. Firstly, current input accuracy is ±0.642% from 0 to 60 degrees Celsius. In addition, voltage input accuracy is ±0.504% under the same conditions. Specifically, output accuracy is ±0.541% for reliable control signals. Consequently, the 1746-NIO4I delivers consistent performance without frequent recalibration.
Drift Specifications
The 1746-NIO4I exhibits low drift with temperature changes. Firstly, current input drift is ±79 ppm per 5 degrees Celsius. In addition, voltage input drift is ±63 ppm per degree Celsius. Specifically, output drift is ±70 ppm per degree Celsius. Consequently, the 1746-NIO4I remains stable across seasonal temperature variations.
Noise Rejection and Isolation
High Common Mode Rejection
The 1746-NIO4I provides excellent noise rejection for accurate measurements. Firstly, common mode rejection is 105 dB at 60 Hertz. In addition, normal mode rejection is 55 dB at 60 Hertz. Specifically, the common mode voltage range is -20 to +20 Volts. Consequently, the 1746-NIO4I delivers clean signals even in electrically noisy industrial environments.
500 Volt Isolation Protection
The 1746-NIO4I provides robust isolation between field wiring and backplane. Firstly, the tested voltage isolation is 500 Volts for safety and noise immunity. In addition, this isolation prevents ground loops from affecting analog measurements. Specifically, overvoltage protection is 220V AC (RMS) or 220V DC continuous. Consequently, the 1746-NIO4I protects the SLC 500 backplane from field wiring faults.
Power Consumption and Physical Specifications
Backplane Current Draw
The 1746-NIO4I consumes modest power from the SLC 500 chassis. Firstly, the backplane current at 5 Volts is 55 milliamps. In addition, the backplane current at 24 Volts is 145 milliamps. Specifically, this low consumption leaves ample power budget for other modules. Consequently, you can install multiple analog modules without exceeding chassis power limits.
Environmental Ratings
The 1746-NIO4I operates in standard industrial conditions. Firstly, the operating temperature range is 0 to 60 degrees Celsius. In addition, the relative humidity range is 5% to 95% non-condensing. Specifically, these ratings cover most factory and control room environments. Consequently, the 1746-NIO4I does not require special cooling or protection in typical installations.
Technical Specifications of the 1746-NIO4I
General Specifications
Manufacturer: Rockwell Automation.
Brand: Allen-Bradley.
Part Number / Catalog No.: 1746-NIO4I.
Series: SLC 500.
Module Type: Analog Combination Module.
UPC: 10662073735882.
UNSPSC: 32151705.
Channel Specifications
Number of Inputs: 2.
Number of Outputs: 2.
Input Type: Differential voltage or current.
Output Type: Current.
Input Signal Specifications
Input Voltage Range: -10 to +10V DC.
Input Current Range: -20 to +20 mA.
Maximum Allowable Input: -30 to +30 mA.
Voltage Input Impedance: 760 kOhms.
Current Input Impedance: 250 Ohms.
Output Signal Specifications
Output Current Range (Normal): 0 to 20 mA.
Output Over-range Capability: 5%.
Output Load Range: 0 to 500 mA.
Resolution Specifications
Input Converter Resolution: 16 bits.
Output Converter Resolution: 14 bits.
Voltage Resolution per LSB: 305 microVolts.
Current Resolution per LSB: 1.22 microAmps.
Output Resolution per LSB: 2.56348 microAmps.
Repeatability: ±1 LSB.
Output Non-Linearity: 0.05%.
Raw Data Scaling
Current Input Raw Data Range: -16,384 to +16,384.
Voltage Input Raw Data Range: -32,768 to +32,767.
Performance Specifications
Bandwidth: 10 Hertz.
Update Time: 512 microseconds (aggregate for all channels).
Input Step Response: 60 milliseconds.
Output Step Response: 2.5 milliseconds.
Accuracy Specifications (0 to 60°C)
Current Input Accuracy: ±0.642%.
Current Input Drift: ±79 ppm / 5°C.
Voltage Input Accuracy: ±0.504%.
Voltage Input Drift: ±63 ppm / °C.
Output Accuracy: ±0.541%.
Output Drift: ±70 ppm / °C.
Rejection Specifications
Common Mode Voltage Range: -20 to +20 Volts.
Common Mode Rejection (60 Hz): 105 dB.
Normal Mode Rejection (60 Hz): 55 dB.
Power Specifications
Backplane Current (5 Volts): 55 mA.
Backplane Current (24 Volts): 145 mA.
Isolation Specifications
Tested Isolation Voltage: 500 Volts.
Isolation Type: Field wiring to backplane.
Overvoltage Protection: 220V AC (RMS) or 220V DC continuous.
Environmental Specifications
Operating Temperature: 0 to 60 degrees Celsius.
Relative Humidity: 5% to 95% non-condensing.
Installation Guide for the 1746-NIO4I
Follow these steps for a proper installation of the 1746-NIO4I.
Step 1: Slot Selection
Firstly, select any available slot in your SLC 500 main chassis. The 1746-NIO4I cannot be installed in slot 0 where the CPU resides. For expansion or remote I/O stations, slot 0 is reserved for communication adapters. Therefore, choose slot 1 or higher for this module.
Step 2: Module Installation
After that, insert the 1746-NIO4I into the chosen slot. Align the module with the card guides on the top and bottom. Then, push firmly until the module seats completely in the backplane connector. Secure the module using the retaining screws.
Step 3: Input Device Wiring
Then, connect your analog sensors to the 1746-NIO4I input terminals. For voltage inputs, connect the signal wire to the appropriate terminal. For current inputs, ensure the loop has an external power source. The input impedance is 250 Ohms for current and 760 kOhms for voltage.
Step 4: Output Device Wiring
Furthermore, connect your analog actuators to the 1746-NIO4I output terminals. The current outputs require a load between 0 and 500 mA. Wire the output positive to the actuator positive terminal. Then, connect the actuator negative to the output common.
Step 5: Configuration and Testing
Finally, apply power to the SLC 500 system. Configure the input and output channels in your PLC program. Verify raw data values match the expected signal ranges. Test each input with a known signal source. Command each output and verify the actuator responds correctly.
Packaging List for the 1746-NIO4I
1746-NIO4I Analog Combination Module (1 unit)
Product documentation and installation guide (1 copy)
Frequently Asked Questions (FAQs) About the 1746-NIO4I
Q1: How many input and output channels does the 1746-NIO4I have?
The 1746-NIO4I provides two input channels and two output channels. The inputs accept either voltage or current signals. The outputs are dedicated current channels only. Therefore, one module handles both analog measurement and control.
Q2: What is the input resolution of the 1746-NIO4I?
The 1746-NIO4I input converter has 16-bit resolution. The voltage resolution is 305 microVolts per LSB. The current resolution is 1.22 microAmps per LSB. Consequently, this module provides high precision for critical analog measurements.
Q3: What is the update time for the 1746-NIO4I?
The 1746-NIO4I has an aggregate update time of 512 microseconds for all channels. The input step response is 60 milliseconds. The output step response is 2.5 milliseconds. Therefore, this module supports responsive control applications.
Q4: Can the 1746-NIO4I be installed in slot 0 of an SLC 500 chassis?
No, it cannot. The 1746-NIO4I cannot be installed in slot 0 where the CPU is mounted. For remote I/O stations, slot 0 is reserved for communication adapters. Therefore, install this module in slot 1 or higher.
Q5: What is the isolation rating of the 1746-NIO4I?
The 1746-NIO4I has a tested isolation voltage of 500 Volts between field wiring and backplane. This isolation prevents ground loops and protects the CPU from field faults. Therefore, accurate readings are maintained in electrically noisy environments.
Welcome to learn about our business. We are a leading global provider of automation equipment and will provide you with complete and cost-effective product solutions. You are welcome to choose us, and our services will make you a long-term partner like our other customers.
Now please let us know your needs and suggestions.
About Ubest
Ubest Automation is a leading global provider of automation products, with deep partnerships with major automation manufacturers to provide customers with customized business solutions, cost-effective products, and comprehensive services.
Product Center
Contact Us
Phone:+86 180 3000 5825
Address:Room 7A, No. 59 Hubin North Road, Siming District Xiamen City China
Email: [email protected]
Contact: Klaus
Industry Links