Product Overview
The Bently Nevada 3500/15 133300-01 is a dedicated Power Input Module (PIM). It pairs directly with the Low Voltage DC Power Supply. This half-height module mounts behind its associated power supply. The PIM accepts 20 to 30 Vdc input from an external source. It also provides critical over-voltage protection via an internal fuse. This module is essential for safe and reliable rack power distribution.
Technical Specifications
Input and Power Characteristics
Input Voltage Range: Accepts 20 to 30 Vdc nominal.
Full Rack Current Draw: Supports up to 11.0 A maximum.
Out of Range Protection: Under-voltage does not harm the PIM or supply. Over-voltage causes the fuse to open on the PIM.
Minimum Loading: No minimum rack load is required.
Physical Dimensions
Height: 120.7 mm (4.75 inches)
Width: 25.4 mm (1.0 inch)
Depth: 114.3 mm (4.5 inches)
Weight: 0.34 kg (0.75 lb)
Rack Space Requirements
Environmental Limits
The Bently Nevada 3500/15 133300-01 performs reliably in harsh conditions.
Operating Temperature: -30°C to +65°C (-22°F to +150°F)
Storage Temperature: -40°C to +85°C (-40°F to +185°F)
Humidity: 95%, non-condensing
Hazardous Area Approvals
The 133300-01 carries multiple hazardous area certifications.
cNRTLus Approval
Class I, Zone 2: AEx/Ex nA nC ic IIC T4 Gc
Class I, Zone 2: AEx/Ex ec nC ic IIC T4 Gc
Class I, Division 2: Groups A, B, C, and D
Temperature Code: T4 @ Ta = -20°C to +65°C (-4°F to +149°F)
ATEX/IECEx Approval
Compliance and Certifications
FCC Compliance
Complies with part 15 of the FCC Rules. Operation is subject to two conditions:
EMC Compliance
Electrical Safety
RoHS Compliance
Maritime Approvals
DNV GL: Rules for classification of ships, offshore units, high speed and light craft
ABS: Rules for Steel Vessels Rules and Offshore Units and Structures
Installation Guide
Follow these steps to install the Bently Nevada 3500/15 133300-01.
Power down the entire 3500 rack system completely.
Locate the half-height slot behind the power supply position.
Slide the PIM into the dedicated half-height slot.
Ensure the PIM sits directly behind its associated power supply.
Connect external 20-30 Vdc input power to the PIM terminals.
For redundant configuration, install a second PIM with the second supply.
Power on the system and verify the Supply OK LED on the power supply.
Redundancy Configuration
You can use two 133300-01 modules for high availability systems.
Each power supply requires its own dedicated PIM.
Both PIMs mount directly behind their respective supplies.
Use two separate external DC sources for full input redundancy.
The PIM fuse protects each supply independently.
Package List
1 x Bently Nevada 3500/15 133300-01 Low Voltage DC Power Input Module
1 x Terminal connector kit for DC input wiring
1 x Installation instruction sheet
Common FAQs
Q1: What is the function of the 133300-01 PIM?
A: The Power Input Module connects external DC power to the 3500/15 supply. It also provides over-voltage protection through an internal fuse.
Q2: Does the Bently Nevada 3500/15 133300-01 work with any power supply?
A: No, this PIM only works with the Low Voltage DC Power Supply option. Do not use it with high voltage AC supplies.
Q3: What happens during an over-voltage condition?
A: The fuse on the 133300-01 opens to protect the system. You must replace the PIM after a fuse failure.
Q4: Can I use this PIM in a hazardous area?
A: Yes, the Bently Nevada 3500/15 133300-01 has cNRTLus and ATEX Zone 2 approvals. It is rated for Class I, Division 2 and Zone 2 locations.
Q5: Where does this module mount inside the 3500 rack?
A: The PIM mounts in a special half-height slot directly behind its power supply. Each power supply requires one dedicated PIM behind it.