3500/15 133292-01 Bently Nevada Low Voltage DC Power Supply



Introduction:
Bently Nevada 3500/15 133292-01 is a low voltage DC power supply module. It provides reliable power for the 3500 monitoring system. This unit accepts 20 to 30 Vdc input for industrial applications.
Customer Reviews
UBEST Automation – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
Product Attributes:
Notice: For real-time prices and inventory, please click the button below to contact us.
Product Overview
The Bently Nevada 3500/15 133292-01 powers your entire 3500 rack system. This Low Voltage DC Power Supply Module works with a dedicated Power Input Module (PIM). You can install one or two units for redundancy. Two half-height slots on the rack left side hold these supplies. The module operates in extreme temperatures from -30°C to +65°C.
Technical Specifications
Input and Power Characteristics
Input Voltage Range: Accepts 20 to 30 Vdc nominal.
Full Rack Current Draw: Maximum draw is 11.0 A.
Out of Range Protection: Under-voltage does not harm the supply or PIM. Over-voltage opens the fuse on the PIM.
Minimum Loading: No minimum rack load is required for operation.
Output and Status Indication
Front Panel LED: Supply OK LED indicates normal operation.
Redundant Operation: Both half-height slots can hold power supplies simultaneously. This allows for true redundant power configuration.
Physical Dimensions
Height: 120.7 mm (4.75 inches)
Width: 50.8 mm (2.0 inches)
Depth: 251.5 mm (9.9 inches)
Weight: 1.39 kg (3.06 lb)
Rack Space: Occupies two half-height slots on the left side of the rack.
Power Input Module (PIM)
Location: Special half-height module directly behind the associated power supply.
Function: Provides input connections and over-voltage protection via fuse.
Environmental Limits
The Bently Nevada 3500/15 133292-01 handles harsh industrial environments.
Operating Temperature: -30°C to +65°C (-22°F to +150°F)
Storage Temperature: -40°C to +85°C (-40°F to +185°F)
Humidity: 95%, non-condensing
Compliance and Certifications
This power supply module meets multiple international standards.
FCC Compliance
Complies with part 15 of the FCC Rules. Operation is subject to two conditions:
This device may not cause harmful interference.
This device must accept any interference received.
EMC Compliance
Directive: EMC Directive 2014/30/EU
Standards: EN 61000-6-2 (Immunity) and EN 61000-6-4 (Emissions) for Industrial Environments
Electrical Safety
Directive: LV Directive 2014/35/EU
Standard: EN 61010-1
RoHS Compliance
Directive: RoHS Directive 2011/65/EU
Maritime Approvals
DNV GL: Rules for classification of ships, offshore units, high speed and light craft
ABS: Rules for Steel Vessels Rules and Offshore Units and Structures
Installation Guide
Follow these steps to install the Bently Nevada 3500/15 133292-01.
Power down the entire 3500 rack system completely.
Locate the two half-height slots on the left side of the rack.
Slide the power supply module into either slot.
Install the Power Input Module (PIM) directly behind the supply.
Connect 20-30 Vdc input power to the PIM terminals.
For redundancy, install a second supply in the remaining slot.
Power on the system and verify the Supply OK LED is lit.
Redundancy Configuration
You can install two Bently Nevada 3500/15 133292-01 modules for high availability.
Both supplies share the load under normal conditions.
If one supply fails, the other continues to power the rack.
Use two separate external DC sources for full redundancy.
The system operates without interruption during supply replacement.
Package List
1 x Bently Nevada 3500/15 133292-01 Low Voltage DC Power Supply Module
1 x Low Voltage DC Power Input Module (PIM)
1 x Installation manual
1 x Connector kit for DC input wiring
Common FAQs
Q1: What input voltage does the 3500/15 133292-01 require?
A: This Low Voltage DC Power Supply Module accepts 20 to 30 Vdc input. Do not exceed 30 Vdc to avoid PIM fuse damage.
Q2: Can I use two power supplies in one 3500 rack?
A: Yes, the rack has two half-height slots for power supplies. Installing two Bently Nevada 3500/15 133292-01 units provides full redundancy.
Q3: What happens if the input voltage drops too low?
A: Under-voltage does not harm the supply or the PIM. The module simply stops providing output until voltage returns to normal.
Q4: Does this power supply work in cold outdoor environments?
A: Yes, the operating temperature range is -30°C to +65°C. This makes it suitable for cold outdoor installations.
Q5: What maritime certifications does the 3500/15 133292-01 hold?
A: This power supply holds DNV GL and ABS certifications. It is approved for ships, offshore units, and steel vessels.