Honeywell CC-PDIL51 Digital Input 24VDC Module 32 Ch


Introduction:
Honeywell CC-PDIL51 digital input module for 24VDC signals. 32 channels with open wire detection and galvanic isolation.
Customer Reviews
UBEST Automation – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
Product Attributes:
Notice: For real-time prices and inventory, please click the button below to contact us.
Product Overview
The Honeywell CC-PDIL51 is a digital input module for 24VDC signals. It accepts discrete inputs from field devices like sensors and switches. This module belongs to the Honeywell Experion LX or C300 control system family. You get extensive internal diagnostics for complete data integrity. The Honeywell CC-PDIL51 supports optional redundancy for critical applications.
Series: Experion LX / Series C I/O
Product Type: Digital Input Module
Product Category: I/O Modules
Current Price (RMB): ¥3,250
Gross Weight: 0.35 kg
Technical Specifications
The Honeywell CC-PDIL51 provides 32 input channels on one module. Each channel accepts 24VDC signals with clear ON and OFF thresholds.
Input / Output Model Identity
Model: CC-PDIL51 – 24 Volt Digital Input
Non-Redundant IOTA Model: CC-TDIL51 (9 inch)
Redundant IOTA Model: CC-TDIL61 (12 inch)
Channel & Isolation Specifications
Input Channels: 32
Galvanic Isolation (any input terminal to common): 1000 VAC RMS
Isolation Technique: Optical (in IOM)
Power & Voltage Range
DI Power Voltage Range: 18 to 30 VDC
ON Sense Voltage: 13 VDC minimum
ON Sense Current: 3 mA minimum
OFF Sense Voltage: 5 VDC maximum
OFF Sense Current: 1.2 mA maximum
Input Impedance & Response
Input Impedance: 4.2 KΩ
Absolute Delay (Input Filter + Isolation): 5 ms ± 20%
Field Resistance Conditions
Field Resistance for Guaranteed ON: 300 Ω maximum at 15 VDC
Field Resistance for Guaranteed OFF: 30 KΩ minimum at 30 VDC
Key Features & Benefits
The Honeywell CC-PDIL51 includes NO open wire detection for safety. You can select internal or external field power as needed. This module supplies non-incendive field power to devices. It provides onboard excitation power without marshalling power. You get direct or reverse input indication flexibility. The CC-PDIL51 has galvanic isolation rated at 1000 VAC RMS. Optional redundancy improves system availability for critical processes.
Installation Guide
Follow these steps to install the Honeywell CC-PDIL51 correctly.
Select the correct IOTA (CC-TDIL51 for non-redundant or CC-TDIL61 for redundant).
Mount the IOTA in a 9-inch or 12-inch rack as required.
Insert the CC-PDIL51 module into the IOTA until fully seated.
Connect 24VDC field power between 18 and 30 volts.
Wire each field device to the corresponding input channel.
Verify ON condition with field resistance below 300 Ω at 15 VDC.
Check LED indicators for proper channel status after power-up.
Package List
1 x Honeywell CC-PDIL51 digital input module
1 x IOTA connection guide label
2 x Module retaining clips
Frequently Asked Questions (FAQ)
Q1: How many input channels does the CC-PDIL51 provide?
A1: The CC-PDIL51 provides 32 digital input channels. Each channel accepts 24VDC signals from field devices.
Q2: What is the galvanic isolation rating on the Honeywell CC-PDIL51?
A2: The Honeywell CC-PDIL51 has 1000 VAC RMS galvanic isolation. This applies to any input terminal voltage referenced to common.
Q3: Can I use this digital input module in a redundant configuration?
A3: Yes, the CC-PDIL51 supports optional redundancy. You must use the CC-TDIL61 IOTA model for redundant operation.
Q4: What happens if a field wire breaks on a connected device?
A4: The CC-PDIL51 includes NO open wire detection. The module diagnostics will identify the broken wire condition automatically.
Q5: What is the absolute delay time for an input signal on the CC-PDIL51?
A5: The absolute delay across the input filter and isolation is 5 ms ± 20%. This gives you a predictable response time between 4 ms and 6 ms.