Allen-Bradley 1756-OB32 ControlLogix Output Module 32-Point


Introduction:
The 1756-OB32 is a 32-point DC output module for ControlLogix systems. It provides sourcing outputs at 10-31.2 VDC with 0.5A per point and LED status indicators.
Customer Reviews
UBEST Automation – Trusted Global Automation Parts Supplier
We offer a wide range of in-stock industrial automation spare parts. All products come with a 12-month warranty and a 30-day refund for quality issues.
Product Attributes:
Notice: For real-time prices and inventory, please click the button below to contact us.
Product Overview
The Allen-Bradley 1756-OB32 is a high-density discrete output module. It belongs to the ControlLogix series of programmable automation controllers. This module provides 32 sourcing outputs for driving field devices.
Typical output devices include pilot lamps, relays, contactors, panel annunciators, solenoids, buzzers, sirens, horns, and other actuating devices. Therefore, it suits a wide range of industrial control applications.
General Specifications
The 1756-OB32 offers robust output capabilities for ControlLogix systems.
Manufacturer: Rockwell Automation.
Brand: Allen-Bradley.
Series: ControlLogix.
Part Number/Catalog No.: 1756-OB32.
Module Type: DC Output Module.
Number of Outputs: 32-Point.
Voltage Category: 12/24 Volts DC Source (sourcing).
Enclosure: None (open-style).
UPC: 10662468702994.
Voltage and Current Ratings
The 1756-OB32 operates within specified voltage and current ranges.
Operating Voltage Range: 10-31.2 Volts DC.
Voltage Category: 12/24 VDC Source (sourcing configuration only).
Maximum On-State Voltage Drop: 200 mV DC at 0.5 A.
Maximum Off-State Leakage Current: 0.5 mA per point.
Minimum Load Current: 3 mA per point.
Maximum Surge Current per Point: 1 A for 10 ms (repeatable every 2 s at 60°C).
Current Derating
The 1756-OB32 requires current derating at elevated temperatures.
At 50°C (122°F):
Current per Point: 0.5 Amps.
Current per Module: 16 Amps.
At 60°C (140°F):
Current per Point: 0.35 Amps (linear derating).
Current per Module: 10 Amps (linear derating).
Therefore, consider ambient temperature when sizing loads.
Output Delay Times
The 1756-OB32 provides fast switching for discrete outputs.
OFF to ON Delay (Nominal): 60 µs.
OFF to ON Delay (Maximum): 1 ms.
ON to OFF Delay (Nominal): 200 µs.
ON to OFF Delay (Maximum): 1 ms.
Backplane Power Consumption
The 1756-OB32 draws power from the ControlLogix backplane.
Backplane Current (5.1 Volts): 300 milliamps.
Backplane Current (24V): 2 milliamps.
Total Backplane Power: 1.58 Watts.
Power Dissipation (Max at 60°C): 4.8 Watts.
Isolation Voltage: 50 Volts continuous (250V continuous per detailed specs).
Removable Terminal Blocks (RTB)
The 1756-OB32 requires a removable terminal block for field wiring.
Compatible RTBs: 1756-TBCH (cage clamp) or 1756-TBS6H (spring clamp).
Recommended Fuses: 5x20mm 800 mA (Littelfuse p/n SP001.1003 or Schurter p/n 216.800).
RTBs provide modular connection to output devices. During module replacement, the entire RTB is removed and transferred to the replacement module. Consequently, wiring rework is prevented for faster maintenance.
LED Indicators
The 1756-OB32 provides clear visual status indication.
Number of LEDs: 32 (one per output point).
Function: Monitor channel actuation and confirm the controller’s command to the connected load.
Additional LEDs: Module status and individual I/O status.
Hence, operators can quickly identify which outputs are active.
Configurable Features
The 1756-OB32 supports per-point configuration.
Individual Channel Configuration: Yes.
Output Forcing: Supported.
Communication Formats: Scheduled output data, output data, rack optimization, listen-only rack optimization, and listen-only output data.
Fault Mode per Point: Configurable (Hold Last State, On, or Off).
Program Mode per Point: Configurable (Hold Last State, On, or Off).
The default setting for both fault and program modes is Hold Last State.
Environmental Specifications
The 1756-OB32 withstands typical industrial conditions.
Operating Temperature: 0 to 60°C.
Non-Operating (Storage) Temperature: -40 to 85°C.
Installation Guidelines
Install the 1756-OB32 in any slot of a ControlLogix local or remote chassis. First, install and ground the chassis and power supply prior to installing the module. Then, insert the module into an available slot.
Select a compatible RTB: 1756-TBCH (cage clamp) or 1756-TBS6H (spring clamp). Install the RTB onto the module. Connect field devices to the RTB terminals. The module supports sourcing configuration only (outputs supply current to the load).
The module provides 32 outputs in two groups of 16 (36-pin connector). At 50°C, each output can source 0.5A (16A per module). At 60°C, derate to 0.35A per point (10A per module). Use the recommended 800 mA fuse for each output.
What is in the Box
Please inspect all items upon delivery.
Allen-Bradley 1756-OB32 output module.
Installation instruction manual.
Anti-static protective bag.
Note: Removable Terminal Block (1756-TBCH or 1756-TBS6H) is sold separately.
Frequently Asked Questions (FAQ)
1. How many output points does the 1756-OB32 have?
The 1756-OB32 provides 32 discrete output points. The outputs are sourcing type (supply current to the load).
2. What is the output voltage range of this module?
The 1756-OB32 operates from 10 to 31.2 Volts DC. The nominal voltage category is 12/24 VDC source.
3. What RTBs are compatible with this module?
The 1756-OB32 requires either the 1756-TBCH (cage clamp) or 1756-TBS6H (spring clamp) removable terminal block. Therefore, order the RTB separately.
4. What is the current rating per output at 60°C?
At 60°C (140°F), each output on the 1756-OB32 can handle 0.35 Amps. The per-module maximum is 10 Amps at 60°C.
5. Can this module be used in a remote chassis?
Yes. The 1756-OB32 can be installed in any ControlLogix local or remote chassis. It occupies a single slot.